Single-phase center-tapped (or split-phase) transformer has a single-phase input winding and a center-tapped output winding connected to a grounded neutral as seen in the figure below. This model is developed from a three winding single-phase transformer whose polarity of the tertiary winding respect to ground has been inverted to obtain twice the phase-ground voltage between secondary and tertiary. 

...

Single-phase 3W Transformer 

Parameters

Symbol

Description

Unit

ID

Transformer name

unique name

Status

Connect/Disconnect status

Initial value 1 (0 for disconnected)

Number of Phases

Phase count in use

for this model only 1 phase is accepted

Primary winding From

Bus1

Primary side: Bus 1

a unique name

Bus2

Primary side: Bus 2

NOT APPLICABLE

Bus3

Primary side: Bus 3

NOT APPLICABLE

V (kV)

Primary winding nominal voltage (phase-to-ground)

kV

S_base (kVA)

Nominal power in primary side

kVA

Conn. type (*)

Primary winding connection type

for this model only ‘wye’ connection is accepted

Secondary winding To

Bus1

Secondary side: Bus 1

a unique name

Bus2

Secondary side: Bus 2

NOT APPLICABLE

Bus3

Secondary side: Bus 3

NOT APPLICABLE

V (kV)

Secondary winding nominal voltage (phase-to-ground)

kV

S_base (kVA)

Nominal power in secondary side

NOT APPLICABLE

Conn. type (*)

Secondary winding connection type

for this model only ‘wye’ connection is accepted

Tertiary winding To

Bus1

Tertiary side: Bus 1

a unique name

Bus2

Tertiary side: Bus 2

NOT APPLICABLE

Bus3

Tertiary side: Bus 3

NOT APPLICABLE

V (kV)

Tertiary winding nominal voltage (phase-to-ground)

kV

S_base (kVA)

Nominal power in tertiary side

NOT APPLICABLE

Conn. type (*)

Tertiary winding connection type

for this model only ‘wye’ connection is accepted

R_12 (p.u.)

Resistance between primary and secondary windings

p.u.

Xl_12 (p.u.)

Reactance between primary and secondary windings

p.u.

R_23 (p.u.)

Resistance between secondary and tertiary windings

p.u.

Xl_23 (p.u.)

Reactance between secondary and tertiary windings

p.u.

R_31 (p.u.)

Resistance between primary and tertiary windings

p.u

Xl_31 (p.u.)

Reactance between primary and tertiary windings

p.u.

Operation

Type of operation: 0 = normal 3W trx, 1 = center-tapped trx

0 or 1 

...