Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

On this page:

Table of Contents
minLevel1
maxLevel1
outlinefalse
styledefault
typelist
printabletrue

Positive Sequence 2W Transformer

...

Mathblock
alignmentleft
T=\frac{RatioW1}{RatioW2}

...

Parameters

Symbol

Description

Unit

ID

Transformer name

a unique name

Status

Connect/Disconnect status

Initial value 1 (0 for disconnected)

From bus

Primary bus

a unique name

To bus

Secondary bus

a unique name

R (pu)

Resistance between primary bus and secondary bus

network p.u.

Xl (pu)

Reactance between primary bus and secondary bus

network p.u.

Gmag (pu)

Magnetization con­ductance

network p.u.

Bmag (pu)

Magnetization Sus­ceptance

network p.u.

Ratio W1 (pu)

Primary off-nominal ratio

p.u.

Ratio W2 (pu)

Secondary off-nom­inal ratio

p.u.

Phase Shift (deg)

Between primary and secondary bus voltage

Degree

...

This model is a three-winding transformer with tap-changer and phase shift.Positive Sequence 3W Transformer

Parameters

Symbol

Description

Unit

ID

Transformer name

a unique name

Status

Connect/Disconnect status

Initial value 1 (0 for disconnected)

Bus1

Primary bus

a unique name

Bus2

Secondary bus

a unique name

Bus3

Tertiary bus

a unique name

R_12 (pu)

Resistance between primary bus and sec­ondary bus

network p.u.


Xl_12 (pu)

Reactance between primary bus and sec­ondary bus

R_23 (pu)

Resistance between secondary bus and tertiary bus

Xl_23 (pu)

Resistance between secondary bus and tertiary bus

R_31 (pu)

Resistance between primary bus and ter­tiary bus

Xl_31 (pu)

Reactance between primary bus and ter­tiary bus

Gmag (pu)

Magnetization con­ductance

Bmag (pu)

Magnetization sus­ceptance

Ratio W1 (pu)

Primary off-nominal ratio

p.u.

Ratio W2 (pu)

Secondary off-nomi­nal ratio

p.u.

Ratio W3 (pu)

Tertiary off-nominal ratio

p.u.

Phase Shift W1 (deg)

Phase shift of wind­ing 1

Degree

Phase Shift W2 (deg)

Phase shift of wind­ing 2

Degree

Phase Shift W3 (deg)

Phase shift of wind­ing 3

Degree

...