HYGOV is the hydro turbine-governor model implemented in line with references [1-3].

Mask and Parameters

HYGOV Parameters

Expanding the "Block diagram" displays the block diagram in the parameters window.



Name

Description

Unit

Variable = {Possible Values}

R

Permanent droop

pu

0 < R < 0.1

r

Temporary droop

pu

0 < r < 2.0

VELM

Gate velocity limit

pu/s

--

GMAX

Maximum gate opening limit

pu

0 < GMAX ≤ 1.0

GMIN

Minimum gate opening limit

pu

0 ≤ GMIN < 1.0

TR

Governor time constant

s

0.04 < TR < 30

TF

Filter time constant

s

0.04 < TF < 0.1

TG

Servo time constant

s

0.04 < TG < 1.0

TW

Water time constant

s

>0.04

At

Turbine gain

pu

--

Dturb

Turbine damping

pu

--

qNL

No-load flow

pu

--

...

I/O name

Description

Unit

w

Machine actual speed

pu 

VAR

External control reference

pu 


Outputs

I/O name

Description

Unit

Gate_p

Gate position

pu

Pm

Mechanical power output

pu


References

[1] P. Kundur, Power System Stability and Control, New York:McGraw-Hill, 1994.

[2] PSS®E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.

...