Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

The Diesel Generator is composed of a round rotor synchronous machine, a grid connection transformer, a speed governor, a synchronism relay and the excitation and load control.

...

  • Generator

  • Governor

  • Excitation System (IEEE-DC1A)

    • Controllers

    • Exciter and Rectifier

    • Initial Values

  • Load ControllerTransformer

  • Synchronism check

Generator Tab

...

Name

Unit

Description

Proportional and integral gains

-

PI controller gains for load control reactive power function

Output initial values and limits

pu

Initial condition for the output of the controller, and maximum-minimum limits

Transformer Tab

...

Name

Unit

Description

Winding connection on the high side voltage of the transformer

-

Possible connection types for the high voltage windings of the transformer (Y/Yn/Yg/delta (lag or lead) )

Winding connection on the low side voltage of the transformer

-

Possible connection types for the low voltage windings of the transformer (Y/Yn/Yg/delta (lag or lead) )

Transformer core type

-

Possible core types for the transformer (three-single phase transformers/core-type/shell-type)

Simulate saturation

-

check box to indicate if the saturation of the transformer will be taken into account

Transformer parameter units

-

Choose between SI or per unit (pu) values

Nominal power

VA

Rated power of the three-phase transformer

Parameters of the high voltage side of the transformer

V, ohms or pu, H or pu

Rated voltage of the high voltage winding, resistance and inductance of the winding

Parameters of the low voltage side of the transformer

V, ohms or pu, H or pu

Rated voltage of the low voltage winding, resistance and inductance of the winding

Magnetizing resistance of the transformer

ohms or pu

Parallel resistance of the magnetization branch of the transformer

Magnetizing inductance of the transformer

H or pu

Parallel inductance of the magnetization branch of the transformer

Zero-sequence inductance L0 flux path return

H or pu

Zero-sequence inductance for the three-limb core transformer

Saturation curve

A, V.s

Excitation current and flux linkages values of the curve

Synchronism check Tab

...

Name

Unit

Description

Enable

-

Enable/disable the relay operation

Data voltage threshold

%

Threshold limit for the voltage

Delta angle and frequency threshold

degrees, Hz

Threshold limit for the angle and the frequency

Breaker Close time

s

Breaker Closing time

Freezing time

s

The initial time during which the breaker will remain zero i.e. the breaker will be open

Voltage check

-

Voltage check functionality enable/disable

Vmin

% of Vll

Threshold voltage below which Bus/Line considered to be dead/non-energized

Vmax

% of Vll

Threshold voltage above which Bus/Line considered to be live/energized

...

Name

Unit

Description

P ref

pu

Active power reference

Q ref

pu

Reactive power reference

V ref

pu

Voltage reference

w ref

pu

Speed reference

status

-

0 = Disconnected from the grid or 1 = Connected to the grid

Islanded

-

0 = Disabled or 1 = Enabled

V line

Phase-ground voltages (a,b,c) measured on the high voltage side of the transformer located after the breaker of the model

I line

Phase currents (a,b,c) measured on the high voltage side of the transformer located after the breaker of the model

V breaker

Phase-ground voltages (a,b,c) measured on the low voltage side of the transformer located after the breaker of the model

Outputs

Name

Unit

Description

Measurements

kW, kVAr, kV, A, pu

In this port there are 5 signals to monitoring the operation of the block:

1)Power delivered by the diesel generator

2)Reactive power delivered by the diesel generator

3)Voltage RMS at the terminal of the diesel generator

4)Current RMS delivered at the terminal of the diesel generator

5)Reserve reactive power of the diesel generator

A

-

Connection port to phase A of the grid

B

-

Connection port to phase B of the grid

C

-

Connection port to phase C of the grid

...