Parameters Tab

NameDescriptionUnit

Nominal Operating Voltage (Vrms LL)

The nominal inverter output line to line RMS voltage

V

Nominal DC-Link Voltage

The nominal value of DC-link voltage

V

Nominal Frequency

System frequency

Hz

Rated Apparent Power

Inverter nominal three-phase apparent power

VA

Rated Active Power

Inverter nominal three-phase apparent power

W

Grid Support Functions Voltage Reference

Choose between average of three-phase RMS or positive sequence

-

Initial values [Freq, V, P, Q, Vdc]

Give the initializing value to the defined parameters

[Hz, pu, pu, pu, pu]

Sample Time

Timestep of the signal conditioning block

s

Filters Tab

NameDescriptionUnit

Power Measurement Filter Time Constant

Specify the time constant for the power measurement first-order filter

s

DC Link Voltage Measurement Filter Time Constant

Specify the time constant for the DC link voltage measurement  first-order filter

s

PLL Tab

NameDescriptionUnit

Regulator gains [Kp,Ki, Kd]

Specify the proportional, integral, and derivative gains of the internal PID controller. Use the gains to tune the PLL response time, overshoot, and steady-state error performances

-

Time constant for derivative action

Specify the time constant for the first-order filter of the PID derivative block

s

Maximum rate of change of frequency

Specify the maximum positive and negative slope of the signal frequency

Hz/s

Filter cut-off frequency for frequency measurement

Specify the second-order low-pass filter cut-off frequency

Hz

Inputs, Outputs and Signals Available for Monitoring

...

Outputs

NameDescriptionUnit

P

Per unit positive sequence active power evaluated using positive sequence voltage and current followed by a low-pass filter

pu

Q

Per unit positive sequence reactive power evaluated using positive sequence voltage and current followed by a low pass filter

pu

PF

Power factor evaluation using active and reactive power

-

Vg

Three-phase instantaneous grid voltages in per unit

pu

Vrms

RMS value of the three-phase grid voltages in per unit

pu

Ig

Three-phase instantaneous grid currents in per unit

pu

Vdc_pu

Nominal DC link voltage in per unit

pu

Vrms_avg

Average of the RMS value of three-phase grid voltages in per unit

pu

Freq

Frequency of the three-phase grid voltage obtained from PLL

Hz

wt

Angle varying between 0 and 2*pi, synchronized on zero crossings of the fundamental (positive-sequence) of phase A voltage

rad

...