Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Page Content

Table of Contents
minLevel1
maxLevel3
outlinefalse
typelist
printablefalse

...

The Active Power Control block is responsible for regulating the flow of active power through the Point of Common Coupling (PCC), when the microgrid is connected to an external AC-grid, by allowing the user to adjust the active power settings and maintain stability.

Mask and Parameters

The Active Power Controller block contains the following configuration mask:

...

Name

Unit

Description

Sample time

s

Simulation time step

Active Power Diesel limits

pu

Minimum and maximum values for Diesel generation

Active Power BESS limits

pu

Minimum and maximum values available for energy storage using BESS

State of Charge (SoC) limits

pu

Minimum and maximum values of State of Charge

Inner state of charge (SoC) limits

pu

Minimum and maximum values of Inner State of Charge

Inputs, Outputs and Signals Available for Monitoring

Inputs

Name

Unit

Description

P renewable (PV+WT)

pu

Specify the Renewable active power measured or forecasted

P load

pu

Specify the Load active power measured or forecasted

SoC

pu

Specify the State of Charge of the BESS

P PCC

pu

Specify the Active power reference of PCC

Dispatch mode

-

Specify Dispatch mode (0: Load-Following, 1: Cycle-Charging, 2: Power-Smoothing

Islanded

-

Specify island (0) or grid-connected (1) mode

Outputs

Name

Unit

Description

DG P ref

pu

Diesel active power reference

Load shed P ref

pu

Load shed command

Curtail P ref

pu

Renewable active power curtail command

BESS P temp ref

pu

ESS active power reference

PCC P ref

pu

Active power reference for grid

P net

pu

Net active power mismatch

Dispatch mode

-

Dispatch mode (0: Load-Following, 1: Cycle-Charging, 2: Power-Smoothing)