Mask and Parameters
General Parameters
Name | Description | Unit | Variable = {Possible Values} | |||
---|---|---|---|---|---|---|
Description | Use this field to add information about the component |
Description = {'string'} | ||||
EMTP (.pun) file for line parameters calculation | The location (path) of the EMTP file (pun file) containing the line parameters |
File = {'path.name'} | ||||||
L-C units in EMTP (.pun) file | The units from the pun file can be taken using two options | L-C units = { 0, 1} | ||||
mH/km, uF/km {0} | Inductance (L), capacitance (C) | |||||
Ohm/km, uS/km {1} | Inductive reactance (Xl) and capacitive susceptance (1/Xc) | |||||
Line Length | The length of the line | km | length = {0, 1e64} | |||
R | Per unit length resistance |
for each phase (mode) | Ω/km |
R = {'-1e64, 1e64'} | ||||||
L | Per unit length inductance for each phase (mode) | H/km | L = {'-1e64, 1e64'} | |||
C | Per unit length capacitor for each phase (mode) | F/km | C = {'-1e64, 1e64'} | |||
Base power (perPhase) | Base value for PU conversion | MVA per phase |
pBase = { [1, 1e64] } | |||||
Base voltage (rmsLN) | Base value for PU conversion | kV rms LN |
vBase = { [1, 1e64] } | |||||
Base frequency | Base value for PU conversion | Hz |
fBase = { [1, 1e64] } | ||||||
Continuously transposed line | Transposition (Untransposed/Transposed) | transp = { 0, 1} | ||||
No {0} | Untransposed line | |||||
Yes {1} | Transposed line | |||||
Transformation matrix | Transformation matrix between mode current and phase current ([Iphase] = [Ti] x [Imode]); not used in the case of transposed line. | Ti = { [-1e64, 1e64] } |
Ports, Inputs, Outputs and Signals Available for Monitoring
Ports
This component supports a 4-phase transmission line
Name | Description |
---|---|
net_1_1 | Network connection of phase |
1 left (+) |
side | |
net_1_2 | Network connection of phase |
1 right |
side | |
net_2_1 | Network connection of phase |
2 left (+) |
side | |
net_2_2 | Network connection of phase |
2 right |
side | |
net_3_1 | Network connection of phase |
3 left (+) |
side | |
net_3_2 | Network connection of phase |
3 right |
side | |
net_4_1 | Network connection of phase |
4 left (+) side | |
net_4_2 | Network connection of phase |
4 right |
side |
Inputs
None
Outputs
None
Sensors
At acquisition, the signals available by the sensors are:
Name | Description | Unit |
---|---|---|
V_Node(1,2,3,4)_(1,2) | Bus voltage for each phase (1,2,3,4) | V |
I(1,2)_Node(1,2,3,4)_(1,2) | Current for each phase (1,2,3,4) | A |
P(1,2)_Node(1,2,3,4)_(1,2) | Active power for each phase (1,2,3,4) on bus (1,2) | W |
Q(1,2)_Node(1,2,3,4)_(1,2) | Reactive power for each phase (1,2,3,4) on bus (1,2) | VAR |
The (1,2) in the previous table indicates the name of the bus at each end of the line (1 for the left (+) side and 2 for the right side)
Electrical Parameters
Calculation of electrical parameters
The Electrical parameters of CP lines can be calculated by using the Line Generator .
Reference
H. W. Dommel, "Digital computer solution of electromagnetic transients in single and multiphase networks," IEEE Trans. Power App. Syst., vol. pas-88, pp. 388-99, 04/ 1969.