Description

The PI line model is mainly used for short transmission lines. The equivalent circuit is shown below.

It is assumed that the capacitance on both sides are is identical. The RL branches are also coupled.


Panel
borderColor#627781
titleColor#627781
borderWidth1
borderStylesolid
titleTable of Contents
Table of Contents
indent20px
stylecircle
printablefalse


Mask and Parameters

General Parameters

Name

Description

Unit

Variable = {Possible Values}

Description

Use this field to add information about the component


Description = {'string'}

Type

The line data can be taken using Matrix or Sequence parameters  


Matrix/Sequence = { 0, 1}

Matrix {0}

Untransposed line. The data is filled in the matrices

Sequence {1}

Transposed line. The data is filled in the sequences

Line Length

The length of the line

km

length = {0, 1e64}

Base power (perPhase)

Base value for PU conversion

MVA per phase

pBase = { [1, 1e64] }

Base voltage (rmsLN)

Base value for PU conversion

kV rms LN

vBase = { [1, 1e64] }

Base frequecy

Base value for PU conversion

Hz

fBase = { [1, 1e64] }

Matrix Parameters

Name

Description

Unit

Variable = {Possible Values}

Resistance - R

Resistance matrix

Ω/km

R = {'-1e64, 1e64'}

Inductance - L

Inductance matrix

H/km

L = {'-1e64, 1e64'}

Capacitance - C

Capacitance matrix

F/km

= {'-1e64, 1e64'}

Sequence Parameters

Name

Description

Unit

Variable = {Possible Values}

R

Resistance value for Zero and Positive sequences

Ω/km

Rseq = {'-1e64, 1e64'}

L

Inductance value for Zero and Positive sequences

H/km

Lseq = {'-1e64, 1e64'}

C

Capacitance value for Zero and Positive sequences

F/km

Cseq = {'-1e64, 1e64'}

Ports, Inputs, Outputs, and Signals Available for Monitoring

Ports

This component has four 1-phase terminals. It means that only single-phase lines can be connected to its terminals:

Name

Description

net_1_1

Network connection of phase a of the left (+) side

net_1_2

Network connection of phases a of the right side

net_2_1

Network connection of phase b of the left (+) side

net_2_2

Network connection of phases b of the right side

Inputs

None

Outputs

None

Sensors

At acquisition, the signals available by the sensors are:

Name

Description

Unit

I1a

Current flowing into port net_1_1

A

I2a

Current flowing out of port net_2_1

A

I1a

Current flowing into port net_1_2

A

I2b

Current flowing out of port net_2_2

A

Calculation of Electrical Parameters