Introduction

The double blinder OOS (out of step) relay is based on the conventional rate of change of impedance method in order to differentiate a stable and an unstable power swing (out-of-step) using positive sequence impedance.

...

Once a power swing is detected, if this trajectory enters the inner blinder, it is identified as an unstable swing, whereas, if it leaves the outer blinder without entering the inner blinder, it is identified as a stable swing, as shown in the figure below. The relay out-of-step trip (OST) logic can be implemented for unstable swing to trip when the positive impedance trajectory either enters the inner blinder zone (between inner blinders), known as Trip On-The-Way-In (TOWI), or exits the inner blinder zone knows as Trip On-The-Way-Out (TOWO). Image Removed

...

Model Description

...

Input

In order to calculate the positive sequence impedance trajectory, the OOS relay requires the voltage and current magnitude (p.u.) as well as angle (deg).

When the impedance trajectory is not between the inner blinder, Reset =1 will reset the OOS and OST outputs to the Normal Condition as shown in the Relay Logic table below.

Output

The OST trip signal is inverse of the OOS signal to make it compatible with the I/O 'status' pin of Positive Sequence Components.

When an unstable swing is detected, the outputs change from Normal Condition to OOS Detection as per the following Relay Logic table. The OOS Detection state can be reset to Normal Condition using Reset =1 when impedance trajectory is outside the inner blinders.

Relay Logic

State

OOS

OST

Normal Condition

0

1

OOS Detection

1

0

Settings

Image Removed

...

Blinder Angle (deg)

The blinder angle of inclination in degrees (refer to relay characteristic figure above).

Inner Blinder (p.u.)

The perpendicular distance of inner blinder from ZTotal (refer to relay characteristic figure above).

Outer Blinder (p.u.)

The perpendicular distance of outer blinder from ZTotal (refer to relay characteristic figure above).

PSB Delay (ms)

The threshold time delay to distinguish between fault and power swing.

OOS Tripping Logic

This can be set to either '0' or '1'. The OST trip signal gets activated during unstable swing according to set value.
0 : when impedance trajectory enters the inner blinder zone (TOWI)
1 : when impedance trajectory leaves the inner blinder zone (TOWO)

Number of Relays

Specifies the number of relays to be modeled. This relay model can take vector inputs, and thus, can be used as more than one relay.

Example

See inside the subsystem Power System Protection Relays in demo PHASOR-02.