The Active Power Control block is responsible for regulating the flow of active power through the Point of Common Coupling (PCC), when the microgrid is connected to an external AC-grid, by allowing the user to adjust the active power settings and maintain stability.
Mask and Parameters
The Active Power Controller block contains the following configuration mask:
...
Name | Unit | Description |
---|---|---|
Sample time | s | Simulation time step |
Active Power Diesel limits | pu | Minimum and maximum values for Diesel generation |
Active Power BESS limits | pu | Minimum and maximum values available for energy storage using BESS |
State of Charge (SoC) limits | pu | Minimum and maximum values of State of Charge |
Inner state of charge (SoC) limits | pu | Minimum and maximum values of Inner State of Charge |
Inputs, Outputs and Signals Available for Monitoring
Inputs
Name | Unit | Description |
---|
...
P renewable (PV+WT) | pu | Specify the Renewable active power measured or forecasted |
...
P load | pu | Specify the Load active power measured or forecasted |
SoC | pu | Specify the State of Charge of the BESS |
...
P PCC | pu | Specify the Active power reference of PCC |
...
Dispatch mode | - | Specify Dispatch mode (0: Load-Following, 1: Cycle-Charging, 2: Power-Smoothing |
...
Islanded | - | Specify island (0) or grid-connected (1) mode |
Outputs
Name | Unit | Description |
---|
...
DG P ref | pu | Diesel active power reference |
...
Load shed P ref | pu | Load shed command |
...
Curtail P ref | pu | Renewable active power curtail command |
...
BESS P temp ref | pu | ESS active power reference |
...
PCC P ref | pu | Active power reference for grid |
...
P net | pu | Net active power mismatch |
...
Dispatch mode | - | Dispatch mode (0: Load-Following, 1: Cycle-Charging, 2: Power-Smoothing) |