The Reactive Power Control block is responsible for regulating the flow of reactive power through the Point of Common Coupling (PCC), when the microgrid is connected to an external AC-grid, by allowing the user to adjust the reactive power settings and maintain stability.

Mask and Parameters

The Reactive Power Controller block contains the following configuration mask:

...

Name

Unit

Description

Reactive Power

pu

Reactive power load of the microgrid in per-unit.

Sample time

s

Simulation time step

Inputs, Outputs and Signals Available for Monitoring

Inputs

Name

Unit

Description

DG Q remaining

pu

Specify the remaining reactive power capacity of the Diesel Generator in per-unit.

DG status

-

Status of the Diesel Generator.

BESS Q remaining

pu

Specify the remaining reactive power capacity of the Battery Energy Storage System in per-unit.

BESS status

-

Status of the Battery Energy Storage System.

WT Q remaining

pu

Specify the remaining reactive power capacity of the Wind Turbine Generation System in per-unit.

WT status

-

Status of theWind Turbine Generation System.

PV Q remaining

pu

Specify the remaining reactive power capacity of the Photovoltaic Generation System in per-unit.

PV status

-

Status of the Photovoltaic Generation System.

Grid Q requirement

pu

Specify the requirement of reactive power from grid.

PHIL Q meas

pu

Specify the reactive power measurement from the PHIL block.

Outputs

Name

Unit

Description

DG Q ref

pu

Reactive power reference of the Diesel Generator.

BESS Q temp ref

pu

Reactive power reference of the Battery Energy Storage System.

WT Q ref

pu

Reactive power reference of the Wind Turbine Generation System.

PV Q ref

pu

Reactive power reference of the Photovoltaic Generation System.