The settings in this tab are used to configure the simulation time-step, required parameters and execution for power-flow calculation, and parameters for dynamic simulation solver. For every configuration changed, click Apply before proceeding.
...
Initialization method | There are three initialization options available for power-flow calculation in the drop-down menu.
|
---|---|
Power mismatch (max p.u.) | Termination condition based on the tolerance of the mismatch equations (default 1E-8). The algorithm terminates if the norm of the mismatch equation becomes smaller than the specified tolerance. |
Max number of NR iterations | Maximum number of iterations allowed for Newton-Raphson to converge (default 100). If the algorithm does not converge once this limit is reached, ePHASORSIM stops and the error message “Power-flow didn’t converge” is displayed. |
Execute | Runs the power flow calculation. |
Execute and export report | Runs the power flow and also writes the results into following output files in a folder with name follows the format: '[XLS file name].PowerFlow'.
|
...