As shown below, to import the data from PowerFactory a DGS XML format file , the model must be first exported using 'DGS_Export_Definitions_5_to_ePH.dz'.
This configuration file is provided in demo PHASOR-17. Note that the DGS version in Export Version must be V5.00 as illustrated below.
...
To use the generated XML file, PowerFactory must be selected from Input file format in the Network data tab of the Solver mask.in the DGS-XML format. The export is configured using a dedicated export definition (or in PowerFactory terminology, a “Variable Section”). Before the actual model can be exported from PowerFactory, the Export Definition must be first imported into the Data Manager:
...
Info |
---|
Notes
|
1. Import of “Export Definition”
Open the Data Manager.
Right-click on the Project -> “Import”.
Select “
” -> “Open”.View file name OPAL-RT UDB Export Definition.pfd For PowerFactory versions 2019 and earlier use
View file name OPAL-RT UDB Export Definition v19.pfd
Optionally select a new destination path via “New Path” in your Data Manager:
As this Export Definition is equal for all projects, it can be imported outside of your PowerFactory project.
Click “OK” to import the export definition
Afterwards a new folder should appear in the project structure
2. Export of Model
Activate the project in the Data Manager.
Open project in PowerFactory main window.
Run a positive sequence AC Load Flow.
...
Select “File” -> “Export” -> “DGS Format...”
Configure the following settings in the DGS-Export dialog:
General tab:
DGS Version: V7.00
Format: XML File
Encoding: UTF-8 (with BOM) (not an option in PowerFactory 2019)
File Name: as you wish (e.g. Your Model.xml)
Variable Sets: OPAL-RT UDB Export Definition (from step 1) (only in 2019 version)
Selection tab (not an option in PowerFactory 2019):
Variable Sets: OPAL-RT UDB Export Definition (from step 1) (only in 2021 and higher versions)
Base Selection: All elements of the active project
Start export by clicking on “Execute”.
Note |
---|
Verify and ensure there is absolutely no error or warning reported in PowerFactory's Output window regarding this process.
OPAL-RT’s Unified Database (UDB). |
3. ePHASORSIM Solver Configuration