Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Table of Contents
maxLevel1
indent20px
stylecircle

...

Parameter tab of 79-AR Relay

NameUnitDescriptionSample value
Operation-79-Recloser enable/disable-
Number of reclosure shots

-

Number of reclosure attempts. Max number of reclosing shots is 3.2
79OI1 Open Interval

sec

Open Interval time for shot 15.0
79OI2 Open Interval

sec

Open Interval time for shot 25.0
79OI3 Open Interval

sec

Open Interval time for shot 35.0
Reclaim time

sec

Duration of reclaim time2.0
CB_Close pulse width

sec

Duration of the circuit breaker closing pulse0.5

...