Mask and Parameters

AVR Parameters

 Image Modified

*Vuel is the usual input for this excitation system (see Inputs, Outputs section below), but the user can choose to use a fixed constant value directly in the mask by choosing “internal” in the mask option.
Expanding the "AC3A diagram" displays the block diagram in the parameters window.

Image Modified

 

NameDescriptionUnit
Tr

Regulator input filter time constant. This input filter is not part of the standard and there are no typical values recommended. It was added for flexibility.

NB: This parameter can be set to zero if the filter is not used.


s
KrConstant associated with regulator and alternator field power supply.
-
Tb

AVR lead-lag numerator time constant

Voltage regulator time constant


s
Tc

AVR lead-lag denominator time constant

Voltage regulator time constant


s
KaAVR filter gain
-
TaAVR filter time constant
s
KfExcitation control system stabilizer gain
-
TfExcitation control system stabilizer time constant
s
VamaxMaximum regulator internal voltage
pu
VaminMinimum regulator internal voltage
pu


Exciter Parameters

Expanding the "Exciter diagram" displays the block diagram in the parameters window.

Image Modified

NameDescriptionUnit
KeExciter constant related to self-excited field
-
TeExciter time constant
s
KcRectifier loading constant
-
KdDemagnetizing factor
-
Se1, Se2Exciter saturation factor at the corresponding Vex
pu
Ve1, Ve2Exciter voltage for the exciter saturation function
pu
KnExcitation system stabgilzer gain
-
EFDNValue at which feedback gain changes
pu
VEmin

Minimum exciter output voltage


pu
VfemaxMaximum exciter field current
pu

...