Table of Contents | ||||||
---|---|---|---|---|---|---|
|
...
Mask and Parameters
AVR Parameters
*Vuel and Voel are the usual inputs for this excitation system (see Inputs, Outputs section below), but the user can choose to use a fixed constant value directly in the mask by choosing “internal” in the mask option.
Expanding the "AC2A diagram" displays the block diagram in the parameters window.
Name | Description | Unit | |
---|---|---|---|
Tr | Regulator input filter time constant. This input filter is not part of the standard and there are no typical values recommended. It was added for flexibility. NB: This parameter can be set to zero if the filter is not used. | s | |
Tb | AVR lead-lag numerator time constant Voltage regulator time constant | s | |
Tc | AVR lead-lag denominator time constant Voltage regulator time constant | s | |
Ka | AVR filter gain Voltage regulator gain | - | |
Ta | AVR filter time constant Regulator time constant | s | |
Kb | Second stage regulator gain | - | |
Kh | High band gain | - | |
Kf | Excitation control system stabilization gain | - | |
Tf | Excitation control system stabilizer time constant | s | |
Vamax | Maximum regulator internal voltage | pu | |
Vamin | Minimum regulator internal voltage | pu | |
Vrmax | Maximum voltage regulator output | pu | |
Vrmin | Minimum voltage regulator output | pu |
Exciter Parameters
Expanding the "Exciter diagram" displays the block diagram in the parameters window.
Name | Description | Unit | |
---|---|---|---|
Te | Exciter time constant | s | |
Ke | Exciter constant related to self-excited field | - | |
Kd | Demagnetization factor | - | |
Kc | Rectifier loading factor | - | |
Se1, Se2 | Exciter saturation factor at the corresponding Vex | pu | |
Ve1, Ve2 | Exciter voltage for the exciter saturation function | pu | |
Vfemax | Maximum exciter field current | pu |
...