Mask and Parameters
Mask
General Tab
Name | Description | Unit | Variable = {Possible Values} | |
---|---|---|---|---|
Name of primary XFO Bus name | Name of the bus on the high voltage side of the static compensator transformer | |||
Primary Transformer voltage | RMS Line-line rated voltage on the primary side of the transformer | kV | {(0,1e12]} | |
Secondary Transformer voltage | RMS Line-line rated voltage on the secondary side of the transformer | V | {(0,1e12]} | |
Leakage reactance | Leakage inductance of the primary winding of the transformer | pu/100MVA | {[0,1]} | |
Delta connection type | Specifies the connection of the transformer and the Delta windings lagging or preceding the Y winding | |||
TCC mode | On = synchronized firing of the TSC capacitive branches, Off = continuous firing | |||
Valve blocking and unblocking | Deblock = valve firing enabled, Block = valve firing disabled | |||
Regulation - Kp | Proportional gain | puB/puV | {[0,1]} | |
Regulation - Ki | Integral gain | puB/puV/s | {(0,1e12]} | |
Regulation - Slope | Slope of voltage controller | pu/100MVA | {[0,1]} | |
Regulation - Hysteresis | Hysteresis | pu/100MVA | {[0,1]} | |
Protection - Strategy Vmax | Maximum value of primary voltage (pu). Above this value, the static compensator is disabled | pu | {[0,1]} | |
Protection - Strategy Vmin_on | Minimum value of primary voltage (pu). Below this value, the static compensator is disabled | pu | {[0,1]} | |
Protection - Strategy Vmin_off | Minimum value of primary voltage (pu) required to enable the static compensator | pu | {[0,1]} | |
AC Fault - Vac_min | Primary voltage threshold (pu) below which a fault is detected | pu | {[0,1]} | |
AC Fault - Fault duration | Fault duration | s | {(0,1e12]} | |
AC Fault - Fault delay | Delay in fault application | s | {(0,1e12]} | |
AC Fault - Under voltage delay | falling edge delay during a specified time interval is applied | s | {(0,1e12]} | |
Disturbance type | Vref or Bref | |||
Disturbance - Delta_Vref | Value of step in the voltage reference | pu | {[0,1]} | |
Disturbance -Delta_Bref | Value of step in the value of the susceptance reference | pu/100MVA | {(0,1e12]} | |
Disturbance -dist_start | Time when the disturbance is applied | s | {(0,1e12]} | |
Disturbance -dist_end | Time when the disturbance is removed | s | {(0,1e12]} | |
Filter - Base frequency | Base frequency | Hz | {(0,100]} | |
Filter -Minimum frequency | Minimum frequency of PLL | Hz | {(0,100]} | |
Filter -Maximum frequency | Maximum frequency of PLL | Hz | {(0,100]} | |
Filter - Bandwidth | Band pass filter bandwidth | Hz | {(0,100]} |
TCR Tab
TCR
Name | Description | Unit | Variable = {Possible Values} | |
---|---|---|---|---|
Connections | Y ground; Y floating; Delta | |||
r | Resistance in parallel with branch reactor | Ohm | {(0,1e12]} | |
L | Series inductance | H | {(0,1e12]} | |
R | Branch resistance | Ohm | {(0,1e12]} | |
Rsnubber | Snubber resistance | Ohm | {(0,1e12]} | |
Csnubber | Snubber capacitance | F | {(0,1e12]} | |
Ropen | Valve resistance when open | Ohm | {(0,1e12]} | |
Rclose | Valve resistance when closed | Ohm | {(0,1e12]} | |
Imin | Chopping current | A | {(0,1e12]} | |
Fbov | Forward break overvoltage | V | {(0,1e12]} | |
Rbov | Reverse break overvoltage | V | {(0,1e12]} | |
Tq | Time for the valve to stop conducting | s | {(0,1e12]} | |
Vmin | Minimum forward voltage across valve to conduct | V | {(0,1e12]} |
TSC Tab
TSC
Name | Description | Unit | Variable = {Possible Values} | |
---|---|---|---|---|
Connections | Y ground; Y floating; Delta | |||
r | Resistance in parallel with branch reactor | Ohm | {(0,1e12]} | |
L | Series inductance | H | {(0,1e12]} | |
R | Branch resistance | Ohm | {(0,1e12]} | |
C | Branch capacitance | F | {(0,1e12]} | |
Rsnubber | Snubber resistance | Ohm | {(0,1e12]} | |
Csnubber | Snubber capacitance | F | {(0,1e12]} | |
Ropen | Valve resistance when open | Ohm | {(0,1e12]} | |
Rclose | Valve resistance when closed | Ohm | {(0,1e12]} | |
Imin | Chopping current | A | {(0,1e12]} | |
Fbov | Forward break overvoltage | V | {(0,1e12]} | |
Rbov | Reverse break overvoltage | V | {(0,1e12]} | |
Tq | Time for the valve to stop conducting | s | {(0,1e12]} | |
Vmin | Minimum forward voltage across valve to conduct | V | {(0,1e12]} |
TCR
Ports
Ports
Name | Description |
---|---|
Port | ABC power signal for connection to other network elements |
Sensors
Name | Description | Unit |
---|---|---|
CMD12phase_x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | Firing pulse of the positive valve in the x branch | |
CMD21phase_x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | Firing pulse of the negative valve in the x branch | |
Iphase_ x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | Current through the branch | A |
STATE12phase_x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | State of the positive valve in the x branch | |
STATE21phase_x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | State of the positive valve in the x branch | |
VphaseTh_x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | Voltage across the valves in the x branch | V |
VCAPphase_x_y where (x= TCR1, TSC1, TSC2, TSC3; y = 1,2,3) | Voltage across the capacitor in the x branch | V |
pulsePat_int | Signal containing the binary code representing the firing orders of the valves | |
VSYNCphase | Voltage signal used by synchronization unit | V |
DelayImpInt | Firing delay (as a fraction of calculation step) calculated by the internal command of the static compensator | |
DelayImpExt | Firing delay (as a fraction of calculation step) calculated by an external command of the static compensator | |
DelayImp | Firing delay (as a fraction of calculation step) sent to the static compensator | |
DelayImpUsed | Firing delay (as a fraction of calculation step) used by the static compensator | |
V_Ref | Voltage reference for the controller | pu |
B_Ref | Susceptance reference for the controller | pu |
Slope | Slope of the controller | |
Deblocked | Signal specifying that the firing pulses are blocked or not | |
TCC_Mode | Signal specifying that the TCC mode is enabled or disabled | |
ManualMode | Signal specifying that the manual mode is enabled or disabled | |
Period | Period of the network (inverse of the frequency) | |
Frequency | Network frequency | Hz |
Alpha_TCR1 | Firing angle of the TCR inductive branch | Degree |
wtphase | Phase angle of synchronization voltages | Degree |
V_Prim | Voltage measured by the system | V |
V_Error | Input of PI regulator of regulation unit | V |
B_SVC | Susceptance seen from primary side of transformer | |
B_TSC | Capacitive susceptance required | |
B_TCR | Inductive susceptance required |