Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Table of Contents
stylenone
image-20240514-174625.pngImage Removedimage-20240614-191551.pngImage Added

Description

This model is based on the PowerSystem Stabilizer (PSS) IEEEST from [1] and [2]. The architecture of the IEEEST is shown below. image-20240515-202656.pngImage Removed

image-20240614-191620.pngImage Added

Mask and Parameters

IEEEST Parameters

image-20240514-180610.pngImage Removedimage-20240614-191650.pngImage Added

Expanding the “Block diagram” displays the IEEEST diagram in the parameters window.

Name

Description

Unit

Input Type

Type of Input (Reference from Input Types Table below)

-

A1, A2, A3, A4, A5, A6

Notch filter Parameters

-

T1, T3

Lead compensating time constants

s

T2, T4

Lag compensating time constants

s

T5, T6

Washout time constant

s

Ks

Stabilizer gains

-

Lsmax

Stabilizer maximum output

pu

Lsmin

Stabilizer minimum output

pu

Vcl

Stabilizer input Vct lower cutoff threshold

pu

Vcu

Stabilizer input Vct upper cutoff threshold

pu

The input of IEEEST can be of any type as mentioned above, based on the control requirements. For each type of input, the corresponding reference input is provided as given in the InputTypes Table.

Input Types Table

Input Type

Name

Description

1

Rotor Speed (pu)

Reference speed (pu) w* of the Syn. generator.

2

Bus frequency (pu)

Reference frequency (pu) f* of the Syn. generator.

3

Generator electrical power on MBASE base (pu)

Reference Electrical power output (pu) Pe0* of the syn. generator.

4

Generator accelerating power (pu) = Pm – Pe0

Reference input = 0

5

Bus voltage (pu)

Reference voltage (pu) Vt*

6

Derivative of pu bus voltage

Reference input = 0

Initial Values

image-20240514-180645.pngImage Removedimage-20240614-191739.pngImage Added

Name

Description

Unit

Input Reference

Reference to the input

-

Inputs, Outputs and Signal Available for Monitoring

Inputs

Name

Description

Unit

Input

The input is one of the following type:

  1. Rotor Speed (pu)

  2. Bus frequency (pu)

  3. Generator Electrical Power in Gen MVA Base (pu)

  4. Generator Accelerating Power (pu)

  5. Bus Voltage (pu)

  6. Derivative of pu bus voltage.

pu

Vct

Compensator terminal voltage of a remote bus for inputs 2, 5 & 6. This may be neglected if the threshold voltages Vcl & Vcu are zero.

pu

Outputs

Name

Description

Unit

Vs

Power system stabilizer model output

pu

References

[1] Siemens Industry, Inc. Siemens Power Technologies International, "PSS®E 34.2.0 MODEL LIBRARY," April 2017.
[2] IEEE, "IEEE Recommended Practice for Excitation System Models for Power System Stability Studies," IEEE Std 421.5-1992, pp. 1-56, 10 Aug. 1992.