Documentation Home Page Hardware Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Current »

This product meets the essential requirements of applicable European Directives as follows:

The essential requirements of the directive 2014/30/EU are covered by the following harmonized standards:
EN61326-1 (2013) – Electrical equipment for measurement, control and laboratory use. The immunity test requirements used for this Product qualification are for the equipment intended to be used in an industrial electromagnetic environment.


Certifying
body
Standard
number
Standard NameSpecificationsMinimum
performance
requirement
criteria

FCC part 15 (2018), subpart BConducted EmissionsClass A 150kHz-30MHz
FCC part 15 (2018), subpart BRadiated EmissionsClass A 30MHz-18GHz

ICES-003 (2016)Radiated EmissionsClass B 30MHz-18GHz
ICES-003 (2016)
 
Conducted EmissionsClass A 150kHz-30MHz










IEC61000-4-2 (2008)
 
Electrostatic Discharge ImmunityContact: ±4kV Air: ±8kVB
IEC61000-4-3 (2006)
A1 (2007)
A2 (2010)
 
Radiated Electromagnetic Field Immunity

80MHz-1000MHz: 10V/m
1.4GHz-2GHz: 3V/m
2GHz-2.7GHz: 1V/m


IEC61000-4-4 (2012)

Electrical Fast Transient Immunity 

Power: ±2kV / 5kHz
I/O Ports: N/A
Communication Ports: ±2kV / 5kHz

B
IEC61000-4-5 (2014)
 
Surge Immunity

Power: ±2kV L-PE / ±1kV L-L
I/O Ports: N/A
Communication Ports: N/A

B
IEC61000-4-6 (2013)


Immunity to Conducted Disturbances,
Induced by Radio-Frequency Fields

Power: 3V
I/O Ports: N/A
Communication Ports: 3V

A
IEC61000-4-8 (2009)

Power Frequency Magnetic Field Immunity Continuous Field: 30A/m / 50Hz & 60HzA
IEC61000-4-11 (2004)Voltage Dips, Short Interruptions and
Voltage Variation Immunity on AC Input

Voltage dips:
0%Un during 1 cycle
40%Un during 10 cycles (at 50Hz)
40%Un during 12 cycles (at 60Hz)
70%Un during 25 cycles (at 50Hz)
70%Un during 30 cycles (at 60Hz)

Short interruptions:
0%Un during 250 cycles(at 50Hz)
0%Un during 300 cycles (at 60Hz)



B
C
C
C
C

C
C

CISPR11 (2015) A1 (2016)

Conducted Emissions Group 1 - class A 150kHz-30MHz
 CISPR11 (2015) A1 (2016)
 
Radiated EmissionsGroup 1 - Class A 30MHz-1GHz
IEC61010-1:2010 (Third edition)


Single fault condition
Protective Conductor Abnormal
Cooling Abnormal
Input
Durability Of Markings
Applied Force
Permissible Limits For Accessible Parts
Impedance Of Protective Bonding Test
Dielectric Voltage Withstand
Humidity Conditioning
Capacitor Discharge
Stability 10 Deg
Static Rigidity
Impact
Drop (Non-Hand Held Equipment)
Temperature
4.4.1
4.4.2.3
4.4.2.10
5.1.3
5.3
6.2.2
6.3
6.5.2.4
6.8
6.8.2
6.10.3
7.4a
8.2.1
8.2.2
8.3.1
10.1-10.4



  


  • No labels