Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Next »


The Active Power Control block is responsible for regulating the flow of active power through the Point of Common Coupling (PCC), when the microgrid is connected to an external AC-grid, by allowing the user to adjust the active power settings and maintain stability.

Mask and Parameters

The Active Power Controller block contains the following configuration mask:

Name

Unit

Description

Sample time

s

Simulation time step

Active Power Diesel limits

pu

Minimum and maximum values for Diesel generation

Active Power BESS limits

pu

Minimum and maximum values available for energy storage using BESS

State of Charge (SoC) limits

pu

Minimum and maximum values of State of Charge

Inner state of charge (SoC) limits

pu

Minimum and maximum values of Inner State of Charge

Inputs, Outputs and Signals Available for Monitoring

Inputs

Name

Unit

Description

Prer

pu

Specify the Renewable active power measured or forecasted

Pload

pu

Specify the Load active power measured or forecasted

SoC

pu

Specify the State of Charge of the BESS

PES

pu

Specify the Active power reference of PCC

Disp_mode

-

Specify Dispatch mode (0: Load-Following, 1: Cycle-Charging, 2: Power-Smoothing

island

-

Specify island (0) or grid-connected (1) mode

Outputs

Name

Unit

Description

Pdsref

pu

Diesel active power reference

Pldref

pu

Load shed command

Prerref

pu

Renewable active power curtail command

Pessref

pu

ESS active power reference

Ppoiref

pu

Active power reference for grid

Pnet

pu

Net active power mismatch

disp_mode

-

Dispatch mode (0: Load-Following, 1: Cycle-Charging, 2: Power-Smoothing)

  • No labels