Introduction
The multiphase line can represent either a 1, 2, or 3-phase line. The impedance parameters of these lines can be presented as positive and zero sequence data or with full matrices. Note that to model the 1 or 2-phase line, only the full matrix presentation is acceptable. Thus, there are four types of multiphase line components in ePHASORSIM native library.
- Single Phase Line
- Two Phase Line
- Three Phase Line with Full Data
- Three Phase Line with Sequential Data
Single Phase Line
Symbol | Description | Unit |
ID | Line name | a unique name |
---|---|---|
Status | Connect/Disconnect status | Initial value 1 (0 for disconnected) |
Length | Length of the line (non-zero) | Any unit |
From1 | First sending bus | a unique name |
To1 | First receiving bus | |
r11 (Ohm/length_unit) | see (*) | ohm/length_unit |
x11 (Ohm/length_unit) | see (*) | |
b11 (uS/length_unit) | see (**) | uS/length_unit |
Two Phase Line
Symbol | Description | Unit |
ID | Line name | a unique name |
---|---|---|
Status | Connect/Disconnect status | Initial value 1 (0 for disconnected) |
Length | Length of the line (non-zero) | Any unit |
From1 | First sending bus | a unique name |
From2 | Second sending bus | |
To1 | First receiving bus | |
To2 | Second receiving bus | |
r11 (Ohm/length_unit) | see (*) | ohm/length_unit |
x11 (Ohm/length_unit) | see (*) | |
r21 (Ohm/length_unit) | see (*) | |
x21 (Ohm/length_unit) | see (*) | |
r22 (Ohm/length_unit) | see (*) | |
x22 (Ohm/length_unit) | see (*) | |
b11 (uS/length_unit) | see (**) | uS/length_unit |
b21 (uS/length_unit) | see (**) | |
b22 (uS/length_unit) | see (**) |
Three Phase Line With Full Data
Symbol | Description | Unit |
ID | Line name | a unique name |
---|---|---|
Status | Connect/Disconnect status | Initial value 1 (0 for disconnected) |
Length | Length of the line (non-zero) | Any unit |
From1 | First sending bus | a unique name |
From2 | Second sending bus | |
From3 | Third sending bus | |
To1 | First receiving bus | |
To2 | Second receiving bus | |
To3 | Third receiving bus | |
r11 (Ohm/length_unit) | see (*) | ohm/length_unit |
x11 (Ohm/length_unit) | see (*) | |
r21 (Ohm/length_unit) | see (*) | |
x21 (Ohm/length_unit) | see (*) | |
r22 (Ohm/length_unit) | see (*) | |
x22 (Ohm/length_unit) | see (*) | |
r31 (Ohm/length_unit) | see (*) | |
x31 (Ohm/length_unit) | see (*) | |
r32 (Ohm/length_unit) | see (*) | |
x32 (Ohm/length_unit) | see (*) | |
r33 (Ohm/length_unit) | see (*) | |
x33 (Ohm/length_unit) | see (*) | |
b11 (uS/length_unit) | see (**) | uS/length_unit |
b21 (uS/length_unit) | see (**) | |
b22 (uS/length_unit) | see (**) | |
b31 (uS/length_unit) | see (**) | |
b32 (uS/length_unit) | see (**) | |
b33 (uS/length_unit) | see (**) |
Three Phase Line With Sequential Data
Symbol | Description | Unit |
ID | Line name | a unique name |
---|---|---|
Status | Connect/Disconnect status | Initial value 1 (0 for disconnected) |
Length | Length of the line (non-zero) | Any unit |
From1 | First sending bus | a unique name |
From2 | Second sending bus | |
From3 | Third sending bus | |
To1 | First receiving bus | |
To2 | Second receiving bus | |
To3 | Third receiving bus | |
R0 (Ohm/length_unit) | Zero-sequence resistance, see (x) | ohm/length_unit |
X0 (Ohm/length_unit) | Zero-sequence reactance, see (x) | |
R1 (Ohm/length_unit) | Positive-sequence resistance, see (x) | |
X1 (Ohm/length_unit) | Positive-sequence reactance, see (x) | |
B0 (uS/length_unit) | Zero-sequence capacitive charge, see (x) | uS/length_unit |
B1 (uS/length_unit) | Positive-sequence capacitive charge, see (x) | uS/length_unit |
(x) If the impedance format is chosen to be sequence data, then Z0 and Z1 must be non-zero.
(*) Configuration of Z matrix (R + j X)
(**) Configuration of B matrix
Available I/O Pins
No | Pin Description | Pin Type | Value/Unit | Instruction |
1 | Set/Get service status | I/O | 1: In-service 0: Out-of-service | lineID/status |
2 | Get sending end current magnitude of wire j | O | A (RMS) | lineID/ImagFromj where j is 1, 2 or 3 |
3 | Get receiving end current magnitude of wire j | O | A (RMS) | lineID/ImagToj where j is 1, 2 or 3 |
4 | Get sending end current angle of wire j | O | Degree | lineID/IangFromj where j is 1, 2 or 3 |
5 | Get receiving end current angle of wire j | O | Degree | lineID/IangToj where j is 1, 2 or 3 |
6 | Get sending end active and reactive power of wire j | O | kW kVAr | lineID/PFromj lineID/QFromj where j is 1, 2 or 3 |
7 | Get receiving end active and reactive power of wire j | O | kW kVAr | lineID/PToj lineID/QToj where j is 1, 2 or 3 |
8 | Get active and reactive power loss of wire j | O | kW kVAr | lineID/PLj lineID/QLj where j is 1, 2 or 3 |
Example
See the Line page in phasor08_IEEE13.xls file in demo PHASOR-08.