ePHASORSIM native library includes five PSS/e supported built-in models for synchronous generators.
- The classical model that only models the mechanical behaviour of machine: SyncGenGENCLS
- The sixth order round rotor detailed model with the impact of exponential saturation: SyncGenGENROE
- The sixth order round rotor detailed model with the impact of quadratic saturation: SyncGenGENROU
- The fifth order salient pole model with the impact of exponential saturation on both axis: SyncGenGENSAE
- The fifth order salient pole model with the impact of quadratic saturation on d-axis: SyncGenGENSAL
SyncGenGENCLS
A constant voltage behind the d-axis transient reactance is used to model a second-order classical synchronous generator. This model is valid for dynamics in few cycles after oscillation, or for generators that are far from the disturbance location.
SyncGenGENCLS Parameters
Symbol | Description | Unit |
Bus | Bus name (Bus ID) | a unique name |
---|
ID | Machine name (Machine ID) | a unique name |
---|
Status | Connect/Disconnect status | 1 for connected 0 for disconnected |
---|
Pg (MW) | Active power | MW |
---|
Qg (MVAr) | Reactive power | MVAr |
---|
Qmin (MVAr) | Minimum reactive power for the machine (for power-flow study) | MVAr |
---|
Qmax (MVAr) | Maximum reactive power for the machine (for power-flow study) | MVAr |
---|
Sbase (MVA) | Power base | MVA |
---|
H (s) | Inertia | second |
---|
D | Damping factor | in machine p.u. |
---|
Ra (pu) | Stator resistance | machine p.u. |
---|
x'_d (pu) | d-axis transient reactance | machine p.u. |
---|
SyncGenGENROE
SyncGenGENROE Parameters
Symbol | Description | Unit |
Bus | Bus name (Bus ID) | a unique name |
---|
ID | Machine name (Machine ID) | a unique name |
---|
Status | Connect/Disconnect status | 1 for connected 0 for disconnected |
---|
Pg (MW) | Active power | MW |
---|
Qg (MVAr) | Reactive power | MVAr |
---|
Qmin (MVAr) | Minimum reactive power for the machine (used in power-flow) | MVAr |
---|
Qmax (MVAr) | Maximum reactive power for the machine (used in power-flow) | MVAr |
---|
Sbase (MVA) | Power base | MVA |
---|
H (s) | Inertia | second |
---|
D | Damping factor | in machine p.u. |
---|
Ra (pu) | Stator resistance | in machine p.u. |
---|
x_d (pu) | d-axis reactance | in machine p.u. |
---|
x_q (pu) | q-axis reactance | in machine p.u. |
---|
x'_d (pu) | d-axis transient reactance | in machine p.u. |
---|
x'_q (pu) | q-axis transient reactance | in machine p.u. |
---|
x"_d (pu) | d-axis sub-transient reactance (x"_d=x"_q) | in machine p.u. |
---|
x_l (pu) | Leakage | in machine p.u. |
---|
T'_do (s) | d-axis transient open-circuit time constant | second |
---|
T"_do (s) | d-axis sub-transient open-circuit time constant | second |
---|
T'_qo (s) | q-axis transient open-circuit time constant | second |
---|
T"_qo (s) | q-axis sub-transient open-circuit time constant | second |
---|
S10 | Saturation function value for 1 p.u. input |
|
---|
S12 | Saturation function value for 1.2 p.u. input |
|
---|
SyncGenGENROU
This model is the equivalent of GENROU in the PSS/e library. It is a sixth-order model with a saturation effect. This model includes transient and sub-transient reactances, one damper winding on the d-axis, and two damper windings on the q-axis.
SyncGenGENROU Parameters
Symbol | Description | Unit |
Bus | Bus name (Bus ID) | a unique name |
---|
ID | Machine name (Machine ID) | a unique name |
---|
Status | Connect/Disconnect status | 1 for connected 0 for disconnected |
---|
Pg (MW) | Active power | MW |
---|
Qg (MVAr) | Reactive power | MVAr |
---|
Qmin (MVAr) | Minimum reactive power for the machine (used in power-flow) | MVAr |
---|
Qmax (MVAr) | Maximum reactive power for the machine (used in power-flow) | MVAr |
---|
Sbase (MVA) | Power base | MVA |
---|
H (s) | Inertia | second |
---|
D | Damping factor | in machine p.u. |
---|
Ra (pu) | Stator resistance | in machine p.u. |
---|
x_d (pu) | d-axis reactance | in machine p.u. |
---|
x_q (pu) | q-axis reactance | in machine p.u. |
---|
x'_d (pu) | d-axis transient reactance | in machine p.u. |
---|
x'_q (pu) | q-axis transient reactance | in machine p.u. |
---|
x"_d (pu) | d-axis sub-transient reactance (x"_d=x"_q) | in machine p.u. |
---|
x_l (pu) | Leakage | in machine p.u. |
---|
T'_do (s) | d-axis transient open-circuit time constant | second |
---|
T"_do (s) | d-axis sub-transient open-circuit time constant | second |
---|
T'_qo (s) | q-axis transient open-circuit time constant | second |
---|
T"_qo (s) | q-axis sub-transient open-circuit time constant | second |
---|
S10 | Saturation function value for 1 p.u. input |
|
---|
S12 | Saturation function value for 1.2 p.u. input |
|
---|
SyncGenGENSAE
SyncGenGENSAE Parameters
Symbol | Description | Unit |
Bus | Bus name (Bus ID) | a unique name |
---|
ID | Machine name (Machine ID) | a unique name |
---|
Status | Connect/Disconnect status | 1 for connected 0 for disconnected |
---|
Pg (MW) | Active power | MW |
---|
Qg (MVAr) | Reactive power | MVAr |
---|
Qmin (MVAr) | Minimum reactive power for the machine (used in power-flow) | MVAr |
---|
Qmax (MVAr) | Maximum reactive power for the machine (used in power-flow) | MVAr |
---|
Sbase (MVA) | Power base | MVA |
---|
H (s) | Inertia | second |
---|
D | Damping factor | in machine p.u. |
---|
Ra (pu) | Stator resistance | in machine p.u. |
---|
x_d (pu) | d-axis reactance | in machine p.u. |
---|
x_q (pu) | q-axis reactance | in machine p.u. |
---|
x'_d (pu) | d-axis transient reactance | in machine p.u. |
---|
x"_d (pu) | d-axis sub-transient reactance (x"_d=x"_q) | in machine p.u. |
---|
x_l (pu) | Leakage | in machine p.u. |
---|
T'_do (s) | d-axis transient open-circuit time constant | second |
---|
T"_do (s) | d-axis sub-transient open-circuit time constant | second |
---|
T"_qo (s) | q-axis sub-transient open-circuit time constant | second |
---|
S10 | Saturation function value for 1 p.u. input |
|
---|
S12 | Saturation function value for 1.2 p.u. input |
|
---|
SyncGenGENSAL
SyncGenGENSAL Parameters
Symbol | Description | Unit |
Bus | Bus name (Bus ID) | a unique name |
---|
ID | Machine name (Machine ID) | a unique name |
---|
Status | Connect/Disconnect status | 1 for connected 0 for disconnected |
---|
Pg (MW) | Active power | MW |
---|
Qg (MVAr) | Reactive power | MVAr |
---|
Qmin (MVAr) | Minimum reactive power for the machine (used in power-flow) | MVAr |
---|
Qmax (MVAr) | Maximum reactive power for the machine (used in power-flow) | MVAr |
---|
Sbase (MVA) | Power base | MVA |
---|
H (s) | Inertia | second |
---|
D | Damping factor | in machine p.u. |
---|
Ra | Stator resistance | in machine p.u. |
---|
x_d (pu) | d-axis reactance | in machine p.u. |
---|
x_q (pu) | q-axis reactance | in machine p.u. |
---|
x'_d (pu) | d-axis transient reactance | in machine p.u. |
---|
x"_d (pu) | d-axis sub-transient reactance (x"_d=x"_q) | in machine p.u. |
---|
x_l (pu) | Leakage | in machine p.u. |
---|
T'_do (s) | d-axis transient open-circuit time constant | second |
---|
T"_do (s) | d-axis sub-transient open-circuit time constant | second |
---|
T"_qo (s) | q-axis sub-transient open-circuit time constant | second |
---|
S10 | Saturation function value for 1 p.u. input |
|
---|
S12 | Saturation function value for 1.2 p.u. input |
|
---|
Available I/O Pins
No | Pin Description | Pin Type | Value/Unit | Instruction |
1 | Get rotor angle | O | Radian | machineID/pins/delta |
2 | Get rotor speed deviation | O | p.u. | machineID/pins/slip |
3 | Get injected current magnitude | O | p.u. (machine base) | machineID/pins/Imag |
4 | Get injected current angle | O | Degree | machineID/pins/Iang |
5 | Get internal voltage magnitude | O | p.u. | machineID/pins/internalVmag |
6 | Get internal voltage angle | O | Degree | machineID/pins/getInternalVang (up to RT-LAB 2023.2)
machineID/pins/internalVang (RT-LAB 2023.3+) |
7 | Set/Get excitation voltage | I/O | p.u. | machineID/pins/Efd |
8 | Set/Get mechanical input torque | I/O | p.u. (machine base) | machineID/pins/Pmech |
9 | Set/Get service status | I/O | 1: In-service 0: Out-of-service | machineID/pins/status |
10 | Get generated active power | O | MW | machineID/pins/Pelec |
11 | Get generated reactive power | O | MVAr | machineID/pins/Qelec |
Example