Documentation Home Page ◇ ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
81 - Frequency Relay
Model Overview
The frequency relay operates whenever the frequency or ROCOF measured from the input voltage signals using a zero-crossing detection logic exceeds the preset settings. A time delay is used to enable the relay to ride through momentary frequency fluctuations and thus prevent nuisance operation. The five-level characteristic of 81O and 81U are presented in figures below:
Characteristics of 81O
Characteristics of 81U
Mask and Parameters
General parameters
Name | Unit | Description |
---|---|---|
Frequency | Hz | The nominal frequency of the measured voltage signals. Both 50 and 60 Hz are supported in the model. |
Freeze Time | s | The freezing time of the 81 relay, when t < freezing time, the 81 relay is not activated. |
Sample Time | s | Block sample time |
Overfrequency
Name | Unit | Description |
---|---|---|
Enable Overfrequency | - | Overfrequency element enable/disable |
Level 1 | Hz | Over-frequency level 1. |
Level 2 | Hz | Over-frequency level 2. |
Level 3 | Hz | Over-frequency level 3. |
Level 4 | Hz | Over-frequency level 4. |
Level 5 | Hz | Over-frequency level 5. |
Time 1 | s | Time delay associated with Level 1. |
Time 2 | s | Time delay associated with Level 2. |
Time 3 | s | Time delay associated with Level 3. |
Time 4 | s | Time delay associated with Level 4. |
Time 5 | s | Time delay associated with Level 5. |
Underfrequency
Name | Unit | Description |
---|---|---|
Enable Underfrequency | - | Underfrequency element enable/disable |
Level 1 | Hz | Under-frequency level 1. |
Level 1 | Hz | Under-frequency level 2. |
Level 1 | Hz | Under-frequency level 3. |
Level 1 | Hz | Under-frequency level 4. |
Level 1 | Hz | Under-frequency level 5. |
Time 1 | s | Time delay associated with Level 1. |
Time 1 | s | Time delay associated with Level 2. |
Time 1 | s | Time delay associated with Level 3. |
Time 1 | s | Time delay associated with Level 4. |
Time 1 | s | Time delay associated with Level 5. |
ROCOF
Name | Unit | Description |
---|---|---|
Enable ROCOF | - | ROCOF element enable/disable |
Level 1 | Hz/s | Rate-of-change-of-frequency level. |
Time 1 | s | Time delay associated with Level 1. |
Inputs and Outputs
Inputs
Name | Description |
---|---|
Vabc | Three-phase voltages |
Reset | The reset signal for the relay. The relay will be reset when this signal becomes 1. |
Outputs
Name | Description |
---|---|
81O | The output of over-frequency relay. By default it is 0, if an over-frequency scenario is detected, it becomes 1. |
81U | The output of under-frequency relay. By default it is 0, if an under-frequency scenario is detected, it becomes 1 |
81R | The output of rate-of-change-of-frequency relay. By default it is 0, if an under-frequency scenario is detected, it becomes 1. |