Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

81 - Frequency Relay

Description

This frequency relay (81) includes three types of frequency elements, namely the over-frequency (81O), the under-frequency (81U) and the rate-of-change-of-frequency (ROCOF) (81R) elements. There are five levels of thresholds available with the 81O and 81U elements, whereas the 81R element features only one level. Each level corresponds to a predefined frequency level and a tripping delay time. When the frequency or ROCOF monitored by the relay exceeds the settings, the relay operates. The model works for 50 Hz or 60 Hz system

Table of Contents

Model Overview

The frequency relay operates whenever the frequency or ROCOF measured from the input voltage signals using a zero-crossing detection logic exceeds the preset settings. A time delay is used to enable the relay to ride through momentary frequency fluctuations and thus prevent nuisance operation. The five-level characteristic of 81O and 81U are presented in figures below:

Characteristics of 81O

Characteristics of 81U

Mask and Parameters

General parameters

NameUnitDescription
FrequencyHzThe nominal frequency of the measured voltage signals. Both 50 and 60 Hz are supported in the model.
Freeze TimesThe freezing time of the 81 relay, when t < freezing time, the 81 relay is not activated.

Sample Time

sBlock sample time

Overfrequency

NameUnitDescription
Enable Overfrequency-Overfrequency element enable/disable
Level 1HzOver-frequency level 1.
Level 2HzOver-frequency level 2.
Level 3HzOver-frequency level 3.
Level 4HzOver-frequency level 4.
Level 5HzOver-frequency level 5.
Time 1sTime delay associated with Level 1.
Time 2sTime delay associated with Level 2.
Time 3sTime delay associated with Level 3.
Time 4sTime delay associated with Level 4.
Time 5sTime delay associated with Level 5.

Underfrequency

NameUnitDescription
Enable  Underfrequency-Underfrequency element enable/disable
Level 1HzUnder-frequency level 1.
Level 1HzUnder-frequency level 2.
Level 1HzUnder-frequency level 3.
Level 1HzUnder-frequency level 4.
Level 1HzUnder-frequency level 5.
Time 1sTime delay associated with Level 1.
Time 1sTime delay associated with Level 2.
Time 1sTime delay associated with Level 3.
Time 1sTime delay associated with Level 4.
Time 1sTime delay associated with Level 5.

ROCOF

NameUnitDescription
Enable ROCOF-ROCOF element enable/disable
Level 1Hz/sRate-of-change-of-frequency level.
Time 1sTime delay associated with Level 1.

Inputs and Outputs

Inputs

NameDescription
VabcThree-phase voltages
ResetThe reset signal for the relay. The relay will be reset when this signal becomes 1.

Outputs

NameDescription
81O

The output of over-frequency relay. By default it is 0, if an over-frequency scenario is detected, it becomes 1.

81U

The output of under-frequency relay. By default it is 0, if an under-frequency scenario is detected, it becomes 1

81R

The output of rate-of-change-of-frequency relay. By default it is 0, if an under-frequency scenario is detected, it becomes 1.

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter