Distance Protection Scheme with Permissive Over-Reaching Transfer Trip (POTT)

Documentation Home Page ◇ ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Distance Protection Scheme with Permissive Over-Reaching Transfer Trip (POTT)

This model presents the implementation of the POTT distance protection scheme in a very simple transmission system. Two 21 MHO relays with identical protection settings are placed at both ends of a 300 km long transmission line (see Fig.1). Both relays are configured with Zone 1 to protect the first 80% of the line, and Zone 2 to protect 120% of the line with a time delay of 200 ms. If any of the computed impedances falls in the protection zone and stays inside for the time delay setting of this zone, the trip signal changes from 0 to 1.

A permissive overreach transfer tripping (POTT) logic is also implemented in this model. For the local relay (R1), when zone 2 picks up, a permissive tripping signal (SPT) will be sent out to the other relay (R2) at the remote end of the line. If the permissive tripping option is enabled on the remote relay (R2), when it receives the permissive tripping signal and detects the fault in its zone 2, it will trip immediately, instead of waiting for the time delay of zone 2. Similarly, if the local relay (R1) receives the permissive tripping signal (RPT) from the remote relay (R2), and detects a fault in its zone 2, it will send out the trip command immediately.

Distance Protection Scheme
Figure 1. - Distance Protection Scheme

Demonstration

In this simulation, a fault is applied 270 km from the left end of the line at t = 1.2s (Fig. 2), so relay 2 pick up in zone 1 (t = 1.2273s) and sends practically without delay the trip command to BR2 while relay 1 pick up in zone 2 and in consequence send the trip command about 200 ms after to BR1 (t = 1.4159s). Since both breakers have received the trip command, they operate by disconnecting both sides of the line. In this case the permissive transfer trip feature was not enabled.

The relays signals and the waveforms of the currents and voltages at both ends of the line (BUS1 and BUS2), are shown in Figures 3 and 4.

System Simulated
Figure 2. - System Simulated
Signals of Breakers and Relays
Figure 3. - Signals of Breakers/Relays
Waveforms of Current and Voltage at Both Ends of the Line
Figure 4. - Waveforms of Current and Voltage at Both Ends of the Line

Carrying out the same test but now enabling the permissive transfer trip feature in both relays (Fig. 5), the results obtained are presented in Figures 6 and 7. It can be seen that by enabling the transferred trip, the relay 1 that sees the fault in the zone 2, trips practically without delay (unlike the previous case) when receiving the transferred trip signal.

Enabling the Permissive Transfer Trip Feature
Figure 5. - Enabling the Permissive Transfer Trip Feature
Signals of Breakers and Relays
Figure 6. - Signals of Breakers/Relays
Waveforms of Current and Voltage at Both Ends of the Line
Figure 7. - Waveforms of Current and Voltage at Both Ends of the Line