Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

BESS Power Reference Compensation

Page Content

This block contains the logic for summing all components of the BESS real power reference. These references are the main reference sent from the real power controller, the PCC real power error, the load reduction compensation, as well as a frequency compensation component calculated in this section which allows the BESS to aid the Diesel Generator in maintaining the Microgrid bus frequency during an islanded condition. This block also contains the logic for summing the reactive power reference components, which are simply the reference sent from the reactive power controller and the PCC reactive power error.

Mask and Parameters

The BESS power reference compensation block contains the following configuration mask with three tabs:

Name

Unit

Description

Name

Unit

Description

Global nominal power

W

The nominal power of the microgrid. Default value is 12e3.

Nominal frequency

Hz

The nominal frequency of the microgrid. Default value is 50.

Sample time

s

Sample time for the discrete-time integrator. The default value is 50e-6.

Name

Unit

Description

Name

Unit

Description

BESS frequency compensation (kW per 0.1 Hz)

kw/Hz

Proportional control factor for BESS frequency compensation. Default value is 3.

Name

Unit

Description

Name

Unit

Description

Time constant

s

Low pass filter time constant for power measurements, in seconds. The default value is 1.

Bypass time

s

Wait time to bypass the filter. The default value is 5.

Start of dead zone

-

Specify dead zone lower limit. Set the value for Start of dead zone less than or equal to End of dead zone. The default value is -2e-3.

End of dead zone

-

Specify dead zone upper limit. Set the value for End of dead zone greater than or equal to Start of dead zone. The default value is 2e-3.

Inputs, Outputs, and Signals Available for Monitoring

Inputs

Name

Unit

Description

Name

Unit

Description

Frequency meas

Hz

The measured frequency of the microgrid.

Islanded

-

Specifies whether the Microgrid is islanded/Grid connected (0 = Grid connected, 1 = islanded)

BESS P temp ref

pu

Active power reference from dispatch controller.

Total load reduction

pu

Total amount of load reduction used to adjust the BESS's power reference. 

Grid P error

pu

The active power difference between the active power transmit through the PCC and what the user demands.

BESS Q temp ref

pu

Reactive power reference from dispatch controller.

Grid Q error

pu

The reactive power difference between the reactive power transmit through the PCC and what the user demands.

Outputs

Name

Unit

Description

Name

Unit

Description

BESS P ref

pu

Active power reference sent to the battery energy storage system.

BESS Q ref

pu

Reactive power reference sent to the battery energy storage system.

 

 

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323