Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Signal Conditioning Three Phase

Page Content

The Signal Conditioning block converts the voltage and current signals, measured at different measurement locations, into their respective per-unit values and transforms them into d-q coordinates. For d-q transformation, Cosine based Park transformation method has been used. This means, that at the beginning (t=0), the d-axis of the rotating frame is aligned with the phase A axis. In addition, the blocks do DC voltage measurement filtering and convert it into its per-unit value. 

Mask and Parameters

The following information is required by the configuration mask of the Signal Conditioning block:

Parameter

Description

Units

Nominal Operating Voltage

The nominal line-to-line RMS voltage of the grid-forming converter 

V

Nominal Power

Nominal Capacity of the grid-forming converter 

VA

Nominal Frequency  

Nominal frequency of the grid-forming converter 

Hz

Nominal DC voltage

The nominal value of the inverter’s input DC voltage

V

DC Link Voltage Measurement Filter Cut-off Frequency

Cut-off frequency of the DC voltage measurement Low Pass Filter

Rad/s

Sample Time

Input sampling period

sec

Inputs, Outputs, and Signals Available for Monitoring

Inputs

Parameter

Description

Units

Iinv

Current measured at the inverter side filtering inductor

A

Io

Output Current, measured at the output of the filter

A

Vo

Per Phase Output voltage, measured across the Filtering Capacitor

V

Vdc

Measured DC Voltage

V

wt

Angle variation with time, synchronized on zero crossings of the fundamental (positive sequence) of phase A

rad

Outputs

Parameter

Description

Units

Frequency

Frequency of the Inverter Output Voltage

pu

Vo (RMS)

RMS value of the output voltage

V

Vo (pu)

Per Phase Output voltage, measured across the Filtering Capacitor

pu

Vodq

Direct and Quadrature axis voltage at the output

pu

Io

Output Current, measured at the output of the filter

pu

Iodq

Direct and Quadrature axis current at the output

pu

Iinv

Current measured at the inverter side filtering inductor

Pu

Iinv_dq

Direct and Quadrature axis current at the inverter side inductor of the filter

pu

Vdc

Measured DC Voltage

pu