Documentation Home Page ◇ HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
3-Winding Impedance-Matrix-Based Transformer with Internal Fault
Mask and Parameters
General Parameters
The base parameters are computed in the Transformer data Tab.
| Description | Use this field to add information and pertinent details about the component |
| Base primary/secondary/tertiary winding voltage (rmsLL) | Base value for PU conversion (kV); defined in Transformer data Tab (kV). Voltage expressed in kV rms LL This base voltage and nominal voltage will change, if the corresponding winding connection switches between delta and Y. |
| Base power (total) | Base value for PU conversion (MVA) |
| Base frequency | Base value for PU conversion (Hz) |
Winding Parameters
The R and L matrices as well as the positive- and zero-sequence parameters are computed in the Transformer data Tab.
| Primary/secondary/tertiary connection | Winding type
|
| Rm - positive sequence | Defined in Transformer data Tab (Ω) |
| Rm - zero sequence | Defined in Transformer data Tab (Ω) |
| [R] | Leakage resistance matrix (Ω) |
| [L] | Leakage inductance matrix (H) |
Fault Parameters
| Faulted winding | (primary or secondary) |
| Leg of faulted winding | (A, B, or C) |
| Fault type | When a fault is enabled, new [L] and [R] matrices are computed but are not displayed in the mask (none, turn-to-ground or turn-to-turn) |
| Fault resistance | (Ω) |
| Fault inductance | (H) |
| Fault turns A | Determines the position of the faulty connection for turn-to-ground faults or turn-to-turn faults in combination with the parameter Fault turns B (% total turns) |
| Fault turns B | Determines the position of the faulty connection for turn-to-turn faults in combination with the parameter Fault turns A (% total turns) |
| Sigma AB | Leakage factor between the two turns A and B of the faulty connection Sigma AB = 1 - MAB2 / (LA * LB) |
| Epsilon | Ratio of leakage factor between faulted winding and other windings Epsilon = Sigma Ai / Sigma fi Sigma Ai: Leakage factor between subwinding A and i Sigma fi: Leakage factor between faulted winding (A+B) and i |
Neutral Impedance Parameters
The neutral impedance parameters are computed in the Transformer data Tab.
| R1, R2, R3 | Neutral resistance of the winding; only applies to Y ground (Ω) |
| L1, L2, L3 | Neutral inductance of the winding; only applies to Y ground (H) |
| C1, C2, C3 | Neutral capacitance of the winding; only applies to Y ground (F) |
Transformer Data
To Learn How to Generate Transformer Parameters See:
Ports, Inputs, Outputs and Signals Available for Monitoring
Ports
| Net_1 | Primary winding connection (supports only 3-phase connections) |
| Net_2 | Secondary winding connection (supports only 3-phase connections) |
| Net_3 | Tertiary winding connection (supports only 3-phase connections) |
| Net_N1 | Neutral connection for primary winding (supports only 1-phase connections) |
| Net_N2 | Neutral connection for secondary winding (supports only 1-phase connections) |
| Net_N3 | Neutral connection for tertiary winding (supports only 1-phase connections) |
| Net_TG | Used for turn-to-ground faults by connecting a 1-phase fault-to-ground component |
| Net_TT | Used for turn-to-turn faults by connecting a 1-phase circuit breaker component between Net_TG and Net_TT |
Inputs
- None
Outputs
- None
Sensors
| IPRIM(a,b,c,n) | Primary current for each phase (A) |
| ISEC2(a,b,c,n) | Secondary current for each phase (A) |
| ISEC3(a,b,c,n) | Tertiary current for each phase (A) |
Fault Modeling
The development and validation of the method is based on [2].
Without any faults, matrices [R] and [L] are 9 x 9.
To modelize a faulted coil between turn and ground or between any two turns, the faulted coil must be divided.
For a turn-to-ground fault, the faulted coil is divided into na and nb.
- na: from top to fault location T1 (in % of nf)
- nb: from fault location T1 to bottom of nf
→ Fault position T1 in % = nb / (na + nb) * 100
Matrices [R] and [L] hence become 10 x 10.
For a turn-to-turn fault, the faulted coil is divided into na, nb and nc.
- na: from top to fault location T1 (in % of nf)
- nb: from fault location T1 to fault location T2 (in % of nf)
- nc: from fault location T2 to bottom of nf
→ Fault position T1 in % = na / (na + nb + nc) * 100
→ Fault position T2 in % = (na + nb) / (na + nb + nc) * 100
Matrices [R] and [L] hence become 11 x 11.
References
[1] Dommel, H., et al., Electromagnetic Transients Program Reference Manual (EMTP Theory Book), 1986
[2] A transformer model for winding fault studies, Patrick Bastard, Pierre Bertrand, Michel Meunier, IEEE, Vol 9, No 2, April 1994
OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter