59 - Overvoltage Relay (1-ph)

Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

59 - Overvoltage Relay (1-ph)


Summary

The over-voltage relay (59-OV) operates when the voltage it monitors exceeds a set of threshold values. There are five levels of settings available in this relay. Each level corresponds
to a predefined over-voltage level and a tripping delay time. The operating quantity of the relay can be the RMS value of phase voltage, or the positive, negative or zero sequence of a three-phase voltage signals. The operating quantity can be either in per unit or actual value. 

Icons and diagrams

Model overview

The over-voltage relay trips electrical equipment under its protection whenever the line voltage exceeds the selected setting. A time-delay is normally used to enable it to ride through momentary spikes and thus prevent nuisance tripping. The five-level over-voltage relay characteristics are presented below. For instance, if we use the default values as illustrated above, Level 1 voltage is 1.05 pu and tripping time is 2 sec. It means that when the input voltage is higher than 1.05 pu and continues to be higher than 1.05 pu for more than 2 seconds, the over-voltage relay will be asserted. If the voltage is higher than 1.05 pu for any time that is less than 2 seconds, its timer will be reset and will not restart until the voltage reaches the level 1 voltage threshold again. All voltage levels and delay times are tunable parameters.

Parameters

The below figure shows the control panel of the 59-OV relay. 

The following parameters are tunable: 

Parameter tab of 59-OV Relay

Name

Unit

Description

Sample value

Name

Unit

Description

Sample value

Level 1

 pu or V

Overvoltage level 1

1.05

Level 2

pu or V

Overvoltage level 2

1.10

Level 3

pu or V

Overvoltage level 3

1.15

Level 4 

pu or V

Overvoltage level 4

1.20

Level 5

pu or V

Overvoltage level 5

1.25

Time 1

sec

Time delay associated with level 1

2

Time 2

sec

Time delay associated with level 2

0.5

Time 3

sec

Time delay associated with level 3

0.4

Time 4 

sec

Time delay associated with level 4

0.3

Time 5

sec

Time delay associated with level 5

0.2

Input and output signals
The module has 1 input and 1 output:

59-OV Relay I/O

I/O Name

Type (Unit) 

Description

I/O Name

Type (Unit) 

Description

V

pu or V

A single dimensional signal,  it should be the RMS value of phase voltage, or the positive, negative or zero sequence of a three-phase voltage signals.

Trip

Binary

The output of overvoltage relay. By default it is 0, if an over-voltage scenario is detected, it becomes 1.