Documentation Home Page ◇ HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
GFM Signal Conditioning Three-Phase
The Signal Conditioning block converts the voltage and current signals, measured at different measurement locations, into their respective per-unit values and transforms them into d-q coordinates. For d-q transformation, Cosine based Park transformation method has been used. This means, that at the beginning (t=0), the d-axis of the rotating frame is aligned with the phase A axis. In addition, the blocks do DC voltage measurement filtering and convert it into its per-unit value.
Mask and Parameters
The following information is required by the configuration mask of the Signal Conditioning block:
Parameter | Description | Units |
Nominal Operating Voltage | The nominal line-to-line RMS voltage of the grid-forming converter | V |
Nominal Power | Nominal Capacity of the grid-forming converter | VA |
Nominal Frequency | Nominal frequency of the grid-forming converter | Hz |
Nominal DC voltage | The nominal value of the inverter’s input DC voltage | V |
DC Link Voltage Measurement Filter Cut-off Frequency | Cut-off frequency of the DC voltage measurement Low Pass Filter | rad/s |
Inputs, Outputs, and Signals Available for Monitoring
Inputs
Parameter | Description | Units |
Iinv | Current measured at the inverter side filtering inductor | A |
Io | Output Current, measured at the output of the filter | A |
Vo | Per Phase Output voltage, measured across the Filtering Capacitor | V |
Vdc | Measured DC Voltage | V |
wt | Angle variation with time, synchronized on zero crossings of the fundamental (positive sequence) of phase A | rad |
Outputs
Parameter | Description | Units |
Frequency_pu | Frequency of the Inverter Output Voltage | pu |
Vo_RMS | RMS value of the output voltage | V |
Vo_dq_pu | Direct and Quadrature axis voltage at the output | pu |
Io_pu | Output Current, measured at the output of the filter | pu |
Io_dq_pu | Direct and Quadrature axis current at the output | pu |
Iinv_pu | Current measured at the inverter side filtering inductor | pu |
Iinv_dq_pu | Direct and Quadrature axis current at the inverter side inductor of the filter | pu |
Vdc_pu | Measured DC Voltage | pu |
Intellectual Property Disclaimer
Natural Resources Canada owns all intellectual property rights in the Smart Inverter Modelling Toolbox software and related products.
OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter