Documentation Home Page ◇ Hardware Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
OP5033XG2 Declaration of Conformity UKCA CE
Declaration of Conformity UKCA CE for the OP5033XG2
Manufacturer Name/Address:
OPAL-RT Technologies Inc.
1751 Richardson, Suite 1060
Montreal, QC H3K 1G6 Canada
www.opal-rt.com
This declaration of conformity is issued under the sole responsibility of: OPAL-RT Technologies Inc.
Product Model/Product
OP5033XG2 with any of the following options:
OP5143-4 Artix-7 PCIe
OP3411 (CAN kit)
OP5455 (Copper PCIe kit)
I350T4V2BLK (Ethernet)
E576T2
Syn1588® PCIe NIC – SFP
X520-SR2 (E10G42BFSR)
PXH830 / PXH832
CP-116E-A / CP-118EL-A
Product Description
Simulator with digital and analog input and output cards intended for indoor use only.
Ratings: 115 VAC ±15 V, 220 VAC ±20 V, 50-60 Hz, 600W max, pollution degree 2
Product Category
Electrical equipment for measurement, control, and laboratory use.
CE Conformity with the Relevant Community Harmonization Legislation
2014/30/EU – Electromagnetic Compatibility Directive
2014/35/EU – Low Voltage Directive
2011/65/EU & (EU) 2015/863 – Restriction of Hazardous Substances (RoHS) in Electrical and Electronic Equipment directive
2012/19/EU – Waste from Electrical and Electronic Equipment (WEEE) Directive
This product is compliant with Regulation (EC) No 1907/2006 (REACH). It contains one or more substances
of very high concern (SVHC) above 0.1% w/w, and all obligations under Article 33(1) have been fulfilled,
including notification to the ECHA SCIP database. https://echa.europa.eu/fr/scip-database
UKCA Conformity with the Relevant Harmonization Legislation
Electromagnetic Compatibility Regulations 2016
Electrical Equipment (Safety) Regulations 2016
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012
References to the standards in relation to which conformity is declared | ||
|---|---|---|
Category | Standards | Test Specifications |
Emissions: | EN 61326-1 (2021) / EN61326-1 (2013) |
|
EN 55011 (2016) A1(2017) | Conducted Emissions: Group 1 - Class A 150 KHz - 30 MHz | |
Immunity: | IEC 61000-4-2 (2008) | Contact: ±4kV |
IEC 61000-4-3 (2020) | 80MHz-1000MHz: 10V/m | |
IEC 61000-4-4 (2012) | Power: ±2 KV / 5 kHz | |
IEC 61000-4-5 (2014) A1 (2017) | Power: ±2 kV L-PE / ±1 kV L-L | |
IEC 61000-4-6 (2013) | Power: 3 V | |
| IEC 61000-4-8 (2009) | Continuous Field: 30 A/m – 50 Hz & 60 Hz |
IEC 61000-4-11 (2020) | Voltage dips: Short interruptions: | |
Safety: | EN 61010-1 :2010/A1 :2019 | Test procedure: CB Scheme |