Documentation Home Page ◇ MMC Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.
Module 1 Introduction to MMC and RT-LAB Solution
- 1 MMC Sub-Module (SM)
- 2 MMC Topology Description
- 3 MMC HB Working Principle
- 4 Recent MMC Projects in China
- 5 Introduction to MMC Projects in China
- 6 MMC Characteristics
- 7 MMC Advantages
- 8 MMC Control Objectives
- 9 MMC Challenges
- 10 OPAL-RT Solution for MMC Simulation
- 11 Multi-rate MMC Model
- 12 Detailed Model of Individual SM
- 13 Key Benefits and Features
- 14 Implementation MMC Model in FPGA
- 15 Hardware Configuration 1
- 16 Optional Implementation MMC Model in CPU
- 17 Connectivity with External Controller
- 18 Example: Fully Hardware in the Loop Test
- 19 Example: Combined HIL and SIL Test
- 20 Summary
MMC Sub-Module (SM)
What is MMC: Modular Multilevel Converter
Submodule (SM) supported in FPGA and CPU:
Half-bridge (HB) SM
Full bridge (FB) SM
Clamp Double (CD) SM
T type (T --) SM
Tailed topologies as requested
HBSM:
FBSM:
CDSM:
T-type SM:
MMC Topology Description
MMC ac-dc converter:
MMC FBSM STATCOM:
MMC HB Working Principle
Sum of all SM capacitor voltage in 1 arm equals two times the dc-link voltage
At any given time, only half SM output their capacitor voltage.
Recent MMC Projects in China
Introduction to MMC Projects in China
Project | Year in | Nb. of | Nb. of SM | Rated DC | Power | Application |
|---|---|---|---|---|---|---|
Nanhui | 2011 | 2 | 50 | 60kV | 18 MVA | Wind Energy |
Nanao | 2013 | 3 | 200 | 320kV | 200 MVA | Power supply for |
Zhoushan | 2014 | 5 | 250 | 400kV | 400 MVA | Power supply for |
Luoping | 2015 | 2 | 200 | ±350kV | 1GVA | Asynchronous |
Xiamen | 2015 | 2 | 400 | ±320 kV | 1GVA | Power supply for |
MMC Characteristics
Arm currents are continuous
Commutating inductors are in arms
Capacitors in each cell (energy storage in MMC)
SM capacitor voltage has to be balanced (on a larger time scale)
DC link voltage is controlled by switch states (fast)
MMC Advantages
Reduced stress on converter and grid component
Low switching frequency reduced switch losses
Low ac harmonic content no need for a filter
Continuous currents in MMC arm and DC link - dc link capacitor omitted
Fast recovery from AC bus short circuit
Fast recovery from DC bus short circuit, but DC breaker or full-bridge converter are needed
Reliability system can remain operating for a certain period even when a few SM are out of order
Can feed loads without any generators (no limit on short circuit ratio)
Easy start-up
Smaller footprint
MMC Control Objectives
Active and reactive power regulation
Capacitor voltage in SM to 1 p.u
Dc link voltage to 1 p.u
Capacitor voltage in all SMs is balanced
Minimize circulating current
Minimize zero-sequence current injecting into the grid
MMC Challenges
New technologies and little engineering experience from existing projects
Complex control and protection systems
Which could be supplied by different manufacturers in multi-terminal systems
Expensive to make and maintain a physical test bench
OPAL-RT Solution for MMC Simulation
MMC simulation in FPGA (250 ns) and grid at tens of microseconds
Optional MMC models on CPU
MMC HB and FB models
MMC application in HVDC or STATCOM
MMC solutions for real time or fast simulation.
MMC HIL and RCP (rapid control prototyping)
Hardware IOs Copper wiring or optical fibers
MMC example controller
Same models in RT LAB or Hypersim platform
Multi-rate MMC Model
Detailed Model of Individual SM
Each of Individual SM is simulated | yes | |
In each SM | ||
Each capacitor voltage controlled individually | yes | |
Discrepancy of SM capacitance values | yes | |
Discharge resistance is simulated | yes | |
Resolution of firing signal | 250 | |
Simulation of dead time | yes | |
Cell short circuit and other faults | yes | |
Forward voltage of diodes | yes | |
Diode non linearity | no | |
Thermal effects due to switching loss of IGBT | Not Yet | |
Key Benefits and Features
MMC FPGA models include up to 1000 SM per valve, 6 valves per converter, multiple number of converters per FPGA, and run at 250 ns;
MMC FPGA modules include features such as: cells short circuit fault, AC fault and DC fault;
FPGA model can also be coupled directly with SFP optical fiber (Small Form factor Pluggable), total bandwidth selectable between 1 and 5 Gbits/s
Minimum latency of 250 ns;
Total update time with actual controller smaller than 4 micros with more than 512 sub modules per optical fiber pairs;
HIL system architecture allow easy I/O expansion;
OPAL RT MMC supports protocols such as Aurora and Gbit Ethernet.
Possibility to implement customized protocol.
Implementation MMC Model in FPGA
Small calculation time step of 250 ns
Large number of SM
up to 1000 SM/valve * 6 valve *2 converter in Kintex 7 (
1000 SM * 6 valve * 2 or more converters in VIRTEX 7 (op7020, op5607) (12,000 cells total) including 16 SFP (5 Gbits/s) with AURORA interface protocol
MMC VBC (low level controller) and communication protocol could be implemented in same FGPA
Support multiple FPGAs for HVDC grids
CPU resources is free to simulate larger AC network because no CPU resource is required
to calculate the MMC cell models
to manage I/O data communication with external controller
Individual control of each IGBT and SM capacitor voltage
Providing SM Vcap debugging mode to help user developing their controller
Supporting both RT LAB and Hypersim Platform
| KINTEX 7 | VIRTEX |
|---|---|---|
No. | 2 | 2 or more |
No. of valves | 6 | 6 |
No. of cells per valve | 1000 | 1000 |
Hardware Configuration 1
OP7020 Virtex 7 FPGA Processor Expansion Unit
Capable of simulating up to 18000 MMC SM
Supports 16 SFP and SFP+ transceivers multimode fiber modules
20 Gbits/s PCI Express x4 links to interface with any OPAL RT real time simulator
OP5607 Virtex 7 FPGA Processor & I/O Expansion Unit
Capable of simulating up to 18000 MMC submodules
Supports 16 SFP and SFP+ transceivers multimode fiber modules.
20 Gbits/s PCI Express x4 links to interface with any OPAL-RT real-time simulator
Up to 8 signal conditioning & A/D converter modules with 16 or 32 channels each
Optional Implementation MMC Model in CPU
Useful for off line simulation of simple system (no FPGA needed) and algorithm development with SIMULINK
Supporting MMC HB and MMC FB
Unlimited number of SM per valve
Several CPU cores are used to calculate the MMC and grid models
1 CPU can solve 300 SM with a time step of 25 μs
Providing SM Vcap debugging mode to help user developing their controller
Connectivity with External Controller
Analog output for V cap and digital input for gating pulses
SFP optical fiber with Aurora protocol at 1 to 5 Gbits/s (16 links per VIRTEX 7 FPGA)
SFP optical fiber with Gigabit Ethernet protocol
Update time between 1 and 5 μ s depending on the number of optical fibers, number of cells and controller manufacturer requirements
Example: Fully Hardware in the Loop Test
Complete control and protection system testing.
Example: Combined HIL and SIL Test
Pole controller and protection testing.
Summary
Challenges | OPAL-RT Solutions |
|---|---|
Very small time step for SM | 250 ns or 500 ns |
Small-time step for AC grid, arm inductors and transformer | 20 to 60 micros using ARTEMIS SSN or HYPERSIM nodal solver |
Very small time step for arm inductor and transformer models | 500 ns to 1 us using eHS FPGA nodal solver |
Large number of SM per converter | 1500 to 18000 cells per FPGA |
Large number of terminal for HVDC grids | Use several FPGA boards (systems with up to 10 FPGA have been delivered) |
Connection to controller with fast rate and small latency | Aurora or Gigabit Ethernet 1 to 5 us update depending on the number of optical fiber links and number of cells |
Accuracy for non-linear elements, e.g. MOV for fault simulation and other large disturbances | Iterative solver |
Tested reliability | Several actual projects |