Decoupling Element
Mask and Parameters
General Parameters:
- Description: Use this field to add all kinds of information about the component
- Decoupling type: V/V, V/I or Line (more information further below)
- Base power (total): Base value pour PU conversion (MVA)
- Base voltage: Base value pour PU conversion (kV)
- rmsLL if connected to 3-ph bus
- rmsLN if only one phase is connected
- Base frequency: Base value pour PU conversion (Hz)
Parameters for all Types:
- Rs: Series resistance; given per phase in V/V and V/I types and per sequence in Line type (ohm)
- Ls: Series inductance; given per phase in V/V and V/I types and per sequence in Line type (H)
Parameters for V/V and V/I Types:
- Grounded phase: Leave blank if no phase is grounded
- Prediction use:
Parameters for Line Type:
- Cs: Total line capacitance ; given per sequence (do not modify this value, it's computed automatically upon building the topology)
- Cs reactive power: Total line capacitance reactive power (do not modify this value, it's computed automatically upon building the topology)
Ports, Inputs, Outputs and Signals Available for Monitoring
Ports
- V: Voltage source side
- V/I: Voltage or current source side, depending on the selected decoupling type
Both ports are power flexible, which means that they will automatically adapt to the number of phases of the network where they are connected (1-phase or 3-phase).
Inputs
- None
Outputs
- None
Sensors
- I: Current in (A) when using in a 1-phase network
- I(a,b,c): Current in (A) for each phase when using in a 3-phase network
Applications
Hint: A good way for decoupling a substation is by replacing the leakage impedance of the substation transformer by a decoupling element in series with the primary winding of the transformer and to transfer the parameter values from one to the other. Be careful though, as depending on the short-circuit power of the simulated network, it may or may not work.
Below are two uses of the decoupling element in a 3-phase power system.
Decoupling of Two Grounded Power Systems
Decoupling of Two Floating Power Systems