Description

In the phase-shifting transformer, the primary and tertiary windings are connected to form a zigzag. The phase shift is specified with respect to the reference winding.

Table of Contents

Mask and Parameters

Phase shift

General Parameters

DescriptionUse this field to add all kinds of information about the component
Base primary/secondary/tertiary winding voltage (rmsLL)

Base value for PU conversion (kV).

  • Voltage expressed in kV rms LL
  • This base voltage and nominal voltage will change, if the corresponding winding connection switches between delta and Y.
Base power (total)Base value for PU conversion (MVA)
Base frequencyBase value for PU conversion (Hz)

Magnetization Impedance Parameters

  • Rm: Equivalent resistance of iron losses of the magnetic circuit (Ω)
  • Lm: Magnetization inductance (H)

Winding Parameters

Secondary connection

Winding type

  • Y ground: Grounded Y connection (can use the internal neutral impedance specified in the other tab)
  • Y floating: Floating Y connection
  • Y neutral: Y connection with impedance connected at the input pin N1 or N2
  • Delta lead: Delta connection with lead of 30°
  • Delta ground: Grounded delta connection (Phase C is grounded)
  • Delta lag: Delta connection with lag of 30°
Voltage (rmsLL)

Rated voltage of the winding (kV)

  • Y connections: Voltage expressed in kV rms LL
  • Delta connections: Voltage expressed in kV rms LL
R1, R2, R3

Leakage resistance of the winding (Ω)

L1, L2, L3

Leakage resistance of the winding (H)

Zigzag Parameters

Phase shift

Amplitude of the phase shift with respect to the reference winding; must be positive (deg)
Voltage (rmsLL)Rated voltage of the zigzag winding (kV)
Voltage phase-shift type Direction of the phase shift with respect to the reference winding (None, Lagging, Leading)


Neutral Impedance Parameters

R2Neutral resistance of the secondary winding; only applies to Y ground (Ω)
L2Neutral inductance of the secondary winding; only applies to Y ground (H)
C2

Neutral capacitance of the secondary winding; only applies to Y ground (F)


Ports, Inputs, Outputs and Signals Available for Monitoring

Ports

Net_1Primary winding connection (supports only 3-phase connections)
Net_2Secondary winding connection (supports only 3-phase connections)
Net_3Tertiary winding connection (supports only 3-phase connections)
Net_NNeutral connection for secondary winding (supports only 1-phase connections)

Inputs

  • None

Outputs

  • None

Sensors

ILMAG(a,b,c)Magnetization current for each phase (A)
IPRIM(a,b,c)Primary current for each phase (A)
ISEC2(a,b,c)Secondary current for each phase (A)
ISEC3(a,b,c)Tertiary current for each phase (A)