Multiphase transformers can represent either a 1, 2, or 3-phase transformer. In the corresponding Excel tab, there are columns for declaration of up to 6 connection points (3 for Winding From end and 3 for Winding To end).
The sending and receiving connection points must be filled in correspondingly:
- For example, if Winding From/Bus 1 is filled, Winding To/Bus 1 must be filled as well.
- The unused connection points can be left empty. However, these empty fields must be located immediately after any completed connection point.
For example, data in which Winding From/Bus 2 and Winding To/Bus 2 fields are filled out but Winding From/Bus 1 and Winding To/Bus 1 are empty is not valid and it causes an error.
Finally, the sending and receiving points can be connected to different phases. For example, Winding From/Bus 1 can be connected to phase A while Winding To/Bus 1 is connected to phase B.
In summary:
To represent a ... | Fill these columns to add connection points... |
---|---|
single-phase transformer | Only Winding From/Bus 1 and Winding To/Bus 1 columns. |
two-phase transformer | The Winding From/Bus1 and Winding From/Bus 2 as well as Winding To/Bus 1 and Winding To/Bus 2. |
three-phase transformer | The Winding From/Bus1, Winding From/Bus 2, Winding From/Bus 3 as well as Winding To/Bus 1, Winding To/Bus 2 and Winding To/Bus 3. |
Multiphase 2W Transformer
Symbol | Description | Unit | |
ID | Transformer name | unique name | |
---|---|---|---|
Status | Connect/Disconnect status | Initial value 1 (0 for disconnected) | |
Number of Phases | Phase count in use | 1, 2, or 3 | |
Winding From | Bus1 | Primary side: Bus 1 | a unique name |
Bus2 | Primary side: Bus 2 | a unique name | |
Bus3 | Primary side: Bus 3 | a unique name | |
V (kV) | Primary winding nominal voltage (phase-to-phase) | kV | |
S_base (kVA) | Nominal power in primary side | kVA | |
Conn. type (*) | Primary winding connection type | ‘wye’ and ‘delta’ | |
Winding To | Bus1 | Secondary side: Bus 1 | a unique name |
Bus2 | Secondary side: Bus 2 | a unique name | |
Bus3 | Secondary side: Bus 3 | a unique name | |
V (kV) | Secondary winding nominal voltage (phase-to-phase) | kV | |
S_base (kVA) | Nominal power in secondary side | NOT APPLICABLE | |
Conn. type (*) | Secondary winding connection type | ‘wye’ and ‘delta’ | |
Tap 1 | Initial tap position: winding 1 | Integer between Lowest and Highest Tap | |
Tap 2 | Initial tap position: winding 2 | ||
Tap 3 | Initial tap position: winding 3 | ||
Lowest Tap | The lowest tap position | Integer value | |
Highest Tap | The highest tap position | Integer value | |
Min Range (%) | Max voltage buck | 0 < value < 100 | |
Max Range (%) | Max voltage boost | value > 0 | |
X (pu) | Total reactance | p.u. | |
Rw1 (p.u.) | Primary winding resistance | p.u. | |
Rw2 (p.u.) | Secondary winding resistance | p.u. |
Multiphase 2W Transformer with Mutual Impedance
Symbol | Description | Unit | |
ID | Transformer name | a unique name | |
---|---|---|---|
Status | Connect/Disconnect status | Initial value 1 (0 for disconnected) | |
Number of Phases | Phase count in use | 1, 2, or 3 | |
Winding From | Bus1 | Primary side: Bus 1 | a unique name |
Bus2 | Primary side: Bus 2 | a unique name | |
Bus3 | Primary side: Bus 3 | a unique name | |
V (kV) | Primary winding nominal voltage (phase-to-phase) | kV | |
S_base (kVA) | Nominal power in primary side | kVA | |
Conn. type (*) | Primary winding connection type | ‘wye’ and ‘delta’ | |
Winding To | Bus1 | Secondary side: Bus 1 | a unique name |
Bus2 | Secondary side: Bus 2 | a unique name | |
Bus3 | Secondary side: Bus 3 | a unique name | |
V (kV) | Secondary winding nominal voltage (phase-to-phase) | kV | |
S_base (kVA) | Nominal power in secondary side | NOT APPLICABLE | |
Conn. type (*) | Secondary winding connection type | ‘wye’ and ‘delta’ | |
Tap 1 | Initial tap position: winding 1 | Integer between Lowest and Highest Tap | |
Tap 2 | Initial tap position: winding 2 | ||
Tap 3 | Initial tap position: winding 3 | ||
Lowest Tap | The lowest tap position | Integer value | |
Highest Tap | The highest tap position | Integer value | |
Min Range (%) | Max voltage buck | 0 < value < 100 | |
Max Range (%) | Max voltage boost | value > 0 | |
Z0 leakage (pu) | Zero-sequence impedance | transformer p.u. | |
Z1 leakage (pu) | Positive-sequence impedance | transformer p.u. | |
X0/R0 | Zero-sequence reactance to resistance ratio | ratio | |
X1/R1 | Positive-sequence reactance to resistance ratio | ratio | |
No Load Loss (kW) | No-load power loss | NOT APPLICABLE |
Note: (*) Four types of winding configurations are supported: 'DD0', 'YgYg0', 'DYg1', 'YgD1'.
Available I/O Pins
No | Pin Description | Pin Type | Value/Unit | Instruction |
1 | Get sending end current magnitude of wire j | O | A (RMS) | transformerID/ImagFromj where j is 1, 2 or 3 |
2 | Get receiving end current magnitude of wire j | O | A (RMS) | transformerID/ImagToj where j is 1, 2 or 3 |
3 | Get sending end current angle of wire j | O | Degree | transformerID/IangFromj where j is 1, 2 or 3 |
4 | Get receiving end current angle of wire j | O | Degree | transformerID/IangToj where j is 1, 2 or 3 |
5 | Set/Get tap position | I/O | Integer between [min_tap, max_tap] | transformerID/tap_j where j is 1, 2 or 3 |
Model Equations
This multiphase transformer is modeled based on the primitive nodal admittance matrix Yprim [1],[2].
Yprim = A N B ZB-1 BT NT AT matrix dimension: np*m x np*m, np = number of phases, m= number of windings
Y1 = B ZB-1 BT ; Yw = N Y1 NT ; Yprim = A Yw AT
Y1 is the ground-referenced nodal admittance matrix on a 1 volt base. Matrix dimension: np*m x np*m
N is the incidence matrix whose non-zero elements are the inverse of the numbers of turns in the windings. This matrix represents the effect of the ideal transformers shown to obtain actual windings voltages. Matrix dimension: 2*np*m x np*m
B is the incidence matrix whose elements are either 1,-1 or 0. It relates currents in the short circuit reference frame where the first winding is assumed shorted to the currents in the nodal admittance reference frame on a 1 volt base. Matrix dimension: np*m x np
A is the incidence matrix whose non-zero elements are generally either 1 and -1, that relates the winding currents to the actual terminal currents. Matrix dimension: nc x 2*np*m, nc = number of terminal currents
ZB is the short circuit impedance matrix. Matrix dimension: np*(m-1) x np*(m-1)
Yw is the winding admittance matrix. Matrix dimension: 2*np*m x 2*np*m
Examples
1) A single-phase 2W transformer with the following data: 7.2/0.12 kV, 25 kVA, X = 20%, R=1.1%
In this case np = 1, m = 2.
ZB in pu = 0.011+0.02i, ZB in 1V base = (ZB in pu)*12/25 kVA = 4.4e-7 + 8e-7i. ZB-1= 527.831e3 - 959.692e3i
Y1 = B ZB-1 BT ; B is a matrix [np*m=2 x np=1]
B =
1 |
-1 |
Y1 =
527.831e3 - 959.692e3i | -527.831e3+959.692e3i |
-527.831e3+959.692e3i | 527.831e3 - 959.692e3i |
N is a matrix [2*np*m=4 x np*m=2]
N =
1 /7200 | 0 |
-1 /7200 | 0 |
0 | 1/120 |
0 | -1/120 |
Yw = N Y1 NT =
0.0102-0.0185i | -0.0102+0.0185i | -0.6109+1.1108i | 0.6109-1.1108i |
-0.0102+0.0185i | 0.0102-0.0185i | 0.6109-1.1108i | -0.6109+1.1108i |
-0.6109+1.1108i | 0.6109-1.1108i | 36.6549-66.6453i | -36.6549+66.6453i |
0.6109-1.1108i | -0.6109+1.1108i | -36.6549+66.6453i | 36.6549-66.6453i |
To generate matrix A is necessary to define the number of terminal currents in the model. In this case there are 2 terminal currents (see the red currents in the figure above) so nc=2 and A matrix is [nc=2 x 2*np*m=4]
A =
1 | 0 | 0 | 0 |
0 | 0 | 1 | 0 |
Finally the matrix Yprim is calculated
Yprim = A Yw AT =
0.0101-0.0185i | -0.6105+1.1100i |
-0.6105+1.1100i | 36.6007-66.5467i |
Below it can be seen how to add this single-phase transformer in the excel file. The total resistance was divided equally between the 2 windings (RW1 = RW2 = 0.011 pu/2 = 0.0055 pu). Note that the voltages voltages must be added as phase to phase voltages even though the model is single-phase (according to the table above)
2) A three-phase 2W transformer with the following data: 12.47/0.208 kV (wye/delta), 75 kVA, X = 20%, R=1.1%
In this case np = 3, m = 2.
ZB in pu = 0.011+0.02i, ZB in 1V base = (ZB in pu)*12/75 kVA = 1.4667e-7 + 2.6667e-7i. ZB-1= 158.349e3 - 287.907e3i (ohms-1)
Y1 = B ZB-1 BT ; B is a matrix [np*m=6 x np=3]
B =
1 | 0 | 0 |
-1 | 0 | 0 |
0 | 1 | 0 |
0 | -1 | 0 |
0 | 0 | 1 |
0 | 0 | -1 |
Y1 =
158.349e3 - 287.907e3i | -158.349e3 + 287.907e3i | 0 | 0 | 0 | 0 |
-158.349e3 + 287.907e3i | 158.349e3 - 287.907e3i | 0 | 0 | 0 | 0 |
0 | 0 | 158.349e3 - 287.907e3i | -158.349e3 + 287.907e3i | 0 | 0 |
0 | 0 | -158.349e3 + 287.907e3i | 158.349e3 - 287.907e3i | 0 | 0 |
0 | 0 | 0 | 0 | 158.349e3 - 287.907e3i | -158.349e3 + 287.907e3i |
0 | 0 | 0 | 0 | -158.349e3 + 287.907e3i | 158.349e3 - 287.907e3i |
N is a matrix [2*np*m=12 x np*m=6]
N =
1 /12470 | 0 | 0 | 0 | 0 | 0 |
-1 /12470 | 0 | 0 | 0 | 0 | 0 |
0 | 1/(208*sqrt(3)) | 0 | 0 | 0 | 0 |
0 | -1/(208*sqrt(3)) | 0 | 0 | 0 | 0 |
0 | 0 | 1 /12470 | 0 | 0 | 0 |
0 | 0 | -1 /12470 | 0 | 0 | 0 |
0 | 0 | 0 | 1/(208*sqrt(3)) | 0 | 0 |
0 | 0 | 0 | -1/(208*sqrt(3)) | 0 | 0 |
0 | 0 | 0 | 0 | 1 /12470 | 0 |
0 | 0 | 0 | 0 | -1 /12470 | 0 |
0 | 0 | 0 | 0 | 0 | 1/(208*sqrt(3)) |
0 | 0 | 0 | 0 | 0 | -1/(208*sqrt(3)) |
Yw = N Y1 NT =
0.0102-0.0185i | -0.0102+0.0185i | -0.3525+0.6409i | 0.3525-0.6409i | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
-0.0102+0.0185i | 0.0102-0.0185i | 0.3525-0.6409i | -0.3525+0.6409i | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
-0.3525+0.6409i | 0.3525-0.6409i | 12.2002-22.1823i | -12.2002+22.1823i | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
0.3525-0.6409i | -0.3525+0.6409i | -12.2002+22.1823i | 12.2002-22.1823i | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | 0.0102-0.0185i | -0.0102+0.0185i | -0.3525+0.6409i | 0.3525-0.6409i | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | -0.0102+0.0185i | 0.0102-0.0185i | 0.3525-0.6409i | -0.3525+0.6409i | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | -0.3525+0.6409i | 0.3525-0.6409i | 12.2002-22.1823i | -12.2002+22.1823i | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | 0.3525-0.6409i | -0.3525+0.6409i | -12.2002+22.1823i | 12.2002-22.1823i | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0.0102-0.0185i | -0.0102+0.0185i | -0.3525+0.6409i | 0.3525-0.6409i |
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | -0.0102+0.0185i | 0.0102-0.0185i | 0.3525-0.6409i | -0.3525+0.6409i |
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | -0.3525+0.6409i | 0.3525-0.6409i | 12.2002-22.1823i | -12.2002+22.1823i |
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0.3525-0.6409i | -0.3525+0.6409i | -12.2002+22.1823i | 12.2002-22.1823i |
To generate matrix A is necessary to define the number of terminal currents in the model. In this case there are 6 terminal currents (see figure above) so nc=6 and A matrix is [nc=6 x 2*np*m=12]
A =
1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 0 |
0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 |
0 | 0 | 0 | 1 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 |
0 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | 1 | 0 |
Yprim = A Yw AT =
0.0101-0.0185i | 0 | 0 | -0.3524+0.6408i | 0.3524-0.6408i | 0 |
0 | 0.0101-0.0185i | 0 | 0 | -0.3524+0.6408i | 0.3524-0.6408i |
0 | 0 | 0.0101-0.0185i | 0.3524-0.6408i | 0 | -0.3524+0.6408i |
-0.3524+0.6408i | 0 | 0.3524-0.6408i | 24.4004-44.3645i | -12.2002+22.1822i | -12.2002+22.1822i |
0.3524-0.6408i | -0.3524+0.6408i | 0 | -12.2002+22.1822i | 24.4004-44.3645i | -12.2002+22.1822i |
0 | 0.3524-0.6408i | -0.3524+0.6408i | -12.2002+22.1822i | -12.2002+22.1822i | 24.4004-44.3645i |
The following image shows how to add this component in the excel file.
3) Multiple transformers in the same model
See the Transformer page in phasor08_IEEE13.xls file in demo PHASOR-08.
References
[1] Roger C. Dugan, "A Perspective on Transformer Modeling for Distribution Systems Analysis". 2003 IEEE Power Engineering Society General Meeting. DOI: 10.1109/PES.2003.1267146