...
Standard coils, discrete inputs, and registers with UINT16, INT16, UINT32, INT32 and FLOAT32 operations are supported. See additional details in the Configuration and Connections sections below.
Supported Features
...
Mode | Select "TCP" or "RTU" depending on how the Modbus slave device is configured to communicate. |
---|---|
Slave ID | ID of the Modbus slave. Each slave must be configured with a unique identification number. This is due to the fact that:
|
TCP specific parameters |
|
RTU specific parameters |
|
Cycle output ratio rate (ms) | Defines the rate (in milliseconds) at which the data from the model is written in the slave's outputs (coils and holding registers). When the slave's outputs are controlled from the model and from the master, this parameter must be set to a value greater than the time step of the model. Otherwise, the write operations made by the master will never be reflected in the model. |
Byte Order | Defines how 32 bits data is encoded. Any of the byte ordering cases are possible (ABCD, BADC, CDAB, DCBA). ABCD refers to the network byte order. |
Permit read/write requests with address gaps | From the lowest address to the highest address configured, this option creates dynamically new coils, discrete inputs, holding registers and input registers at every address that is not defined by the user and assigns a value of 0. |
...