Modbus Slave
Page Content
Description
The Modbus Slave driver allows the simulator to communicate with one or multiple pieces of equipment configured with a Modbus master interface. The simulator can instantiate multiple slaves to which masters can connect and send read/write commands.
The Modbus Slave interface can operate over TCP/IP using an Ethernet physical link or over RTU using a serial link. The user must select the communication protocol matching the network configuration.
Standard coils, discrete inputs, and registers with UINT16, INT16, UINT32, INT32 and FLOAT32 operations are supported. See additional details in the Configuration and Connections sections below.
Supported Features
The following is a list of the features supported by the driver:
Standard registers:
Coils: Available as a model output, a model input (controlled by the master) or both
Discrete inputs: Available as a model output
Input registers: Available as a model output. The supported data types are UINT16, INT16, UINT32, INT32 and FLOAT32
Holding registers: Available as a model output, a model input (controlled by the master) or both. The supported data types are UINT16, INT16, UINT32, INT32 and FLOAT32
Supports TCP and RTU modes
Allows multiple-slave instantiation
Configurable TCP port when operating over TCP mode
Configurable serial port parameters when operating over RTU mode
Supports reconnection with the master device(s) if a connection is lost
TCP mode supports connecting multiple masters to the same slave
TCP mode supports having multiple slaves with the same IP address and TCP port combination; in this scenario, the slave ID is used as the differentiator
Configuration
The driver is entirely configurable via the RT-LAB interface. Users can add, delete, and duplicate Modbus slave devices. Configuring holding registers, input registers, discrete input or coils is also an easy task.
General configuration
The first parameters to be configured are found below:
Use an RT core for asynchronous computation | If set to true, the driver reserves a real-time CPU core for its communication system and is able to handle a bigger amount of data. If set to false, the communication system defaults to core 0. |
---|---|
Verbose | If enabled, additional information is displayed during the loading of the model. |
Slave(s) Configuration
By default, the driver is configured with one TCP slave configured to listen on the internal loopback network on port 1504 and one RTU slave configured on /dev/ttyS0 serial port.
Adding another Modbus slave is easily doable through the RT-LAB GUI.
The following shows a slave configured with TCP/IP.
Each slave device has multiple parameters:
Mode | Select "TCP" or "RTU" depending on how the Modbus slave device is configured to communicate. |
---|---|
Slave ID | ID of the Modbus slave. Each slave must be configured with a unique identification number. This is due to the fact that:
|
TCP specific parameters |
|
RTU specific parameters |
|
Cycle output rate (ms) | Defines the rate (in milliseconds) at which the data from the model is written in the slave's outputs (coils and holding registers). When the slave's outputs are controlled from the model and from the master, this parameter must be set to a value greater than the time step of the model. Otherwise, the write operations made by the master will never be reflected in the model. |
Byte Order | Defines how 32 bits data is encoded. Any of the byte ordering cases are possible (ABCD, BADC, CDAB, DCBA). ABCD refers to the network byte order. |
Permit read/write requests with address gaps | From the lowest address to the highest address configured, this option creates dynamically new coils, discrete inputs, holding registers and input registers at every address that is not defined by the user and assigns a value of 0. |
For each slave instance, the inputs and outputs must be configured. The slave will reply to the master's requests continuously as fast as possible.
The four next sub-sections describe the available data mapping options for the Modbus Slave driver.
Coils
The coil configuration is shown in the image below.
The four modifiable fields are:
Name | A specific name to recognize the coil. |
---|---|
Address | The address at which the slave holds that coil. |
Initial value | If the coil is only controlled by the master, it will take this value (as a binary number) at the beginning of the simulation. Otherwise, the initial value will come from the model. |
Control from | Three options are available.
|
Discrete Inputs
The discrete inputs configuration is shown in the image below.
The two modifiable fields are:
Name | A specific name to recognize the discrete input. |
---|---|
Address | The address at which the slave holds that discrete input. |
Holding Registers
The holding registers configuration is shown in the image below.
The five modifiable fields are:
Name | A specific name to recognize the holding register. |
---|---|
Address | The address at which the slave holds that holding register. |
Initial value | If the holding register is only controlled by the master, it will take this value at the beginning of the simulation. Otherwise, the initial value will come from the model. |
Control from | Three options are available and they work the same way with the holding registers as with the coils.
|
Register type | Multiple options are available.
|
Input Registers
The input registers configuration is shown in the image below.
The three modifiable fields are:
Name | A specific name to recognize the input register. |
---|---|
Address | The address at which the slave holds that input register. |
Register type | Multiple options are available. These are the same options available as for the holding registers.
|
Connections
Once the driver has been configured as desired and associated with the proper model subsystem, the user will have to connect points in the model to points in the driver by using the designated RT-LAB GUI. This connection panel will show all the driver's and model's connectable points, once the model has been compiled. It is also possible to make connections to LabVIEW panels.
The example model provided with RT-LAB is already packaged with connections between the driver and the model. It can be used as an example to understand how the connections between the model and the driver should be done.
The connection points are classified in the following categories:
Coils
Discrete Inputs
Holding Registers
Input Registers
Under each category, the configured operations will show up with the names that have been given by the user in the driver configuration GUI. If the icon is blue, it is a slave output that can be written by a Modbus master and this signal is returned to the simulation at the beginning of each time step. It means that this signal needs to be connected to an OpInput block of the Simulink model.
If the icon is red, it is a model output. It means that this signal needs to be connected to an OpOutput block of the Simulink model.
Take note that if a slave output is configured to be controlled from Both, there will be two connection points instantiated. One will be from Master (blue icon) and the other one will be from Model (red icon). The data point from Master is always directly mapped to the real slave outputs (holding register or coil) and this output will be overwritten by the from Model data point at a time interval determined by the Cycle output ratio (ms).
In TCP mode, an additional "Connected" connection point is available and can be used in the model to indicate if the Modbus slave is connected to a Modbus master or not. It represents the number of Modbus masters currently connected to the Modbus slave. This value will be the same for all slaves sharing an IP address and TCP port combination.
In RTU mode, an additional "Bus Activity" connection point is available and can be used in the model to indicate if the Modbus slave is receiving requests from a Modbus master.
Limitations
The following is a list of the limitations of the driver:
Modbus ASCII is not supported.
An OP3310 RS-232/422/485 PCIe serial card is needed in case it is required to communicate with multiple slaves on the same physical bus in RTU mode.