This document shows the steps of importing a PSS/E model into HYPERSIM.
Table of Contents |
---|
...
Importing a PSSE Network
...
Step 1 - Create a new HYPERSIM model
Select New from File tab, then create a HYPERSIM file.
...
Select the desired folder and choose the file name, then Save it.
...
Step 2 - Import the PSS/E model
The PSS/E import feature can be found in
...
the Network
...
Import tool
...
from
...
...
the HYPERSIM Ribbon Options under the Network section.
...
Select the *.raw file from PSS/E option and Import it.
...
To import a PSS/E model into HYPERSIM, it is necessary to provide the path to the *.raw file (or *.dyr file) must be provided in the designated "File" text field. (Users can also browse for it using the button to the right).All other files with the same name in the same directory are selected automatically. Users can import a model with Alternatively, users can utilize the browse option located on the right-hand side of the field for file selection.
For importing the dynamic data, the *.dyr file must bear the identical name as the *.raw file. The system automatically selects any other files within the same directory that share the same name.
While it is possible to import a model using only a *.raw file, without any an accompanying *.dyr file, but may it is not possible to import only solely a *.dyr file.
The PSS/E Network Import operation generates a set of reports, which are useful, among other things, for:
Identifying any ignored or unsupported components.
Assist OPAL-RT in the identification of the cause of potential conversion issues.
Options:For more details on these reports see Network Import Reports.
Options
...
Replace machines by sources |
If activated, |
this option replaces all machines with ideal voltage sources. |
Non-connected buses in the original circuit will not be imported
Pressing the Import button first analyzes the PSSE circuit and prepares a "edd" file and a python script that uses the Python API. This script will rely on data that will be stored in a folder ConversionReports_YYYY-MM-DD_HH-mm. next to the PSCAD file. The python script is then run and the model will be imported into HYPERSIM.
Group machines with controls | This feature merges the machines and their controllers into a subcircuit. |