The turbine-governor data comes from ElmDsl section in the DGS-XML file. The following tables outline the required parameters for each turbine-governor that is accessible through the Native Library.
Parameter "PN" for all Turbine Governor models and "At" for TGOV1 are not imported. Their values must be set to PN = 0 and At = 1.
The governors that have
gov_
prefixes are from the PSSE compatible library in PowerFactory 2022 and prior versions. Comparatively, the governors that havegov_PSSE_
prefixes are from the PSSE compatible library in PowerFactory 2023 and more recent versions.
The version of the Governor components can be determined using the following pattern:
Version | Type Prefixes |
---|---|
PowerFactory 2022 and prior versions | Governors: gov_ |
PowerFactory 2023 and more recent versions | Governors: gov_PSSE_ |
gov_GAST, gov_PSSE_GAST
These PowerFactory components are mapped to GAST component of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Speed Droop [pu] | Any value |
| Controller Time Constant [s] | |
| Actuator Time Constant [s] | |
| Compressor Time Constant [s] | |
| Ambient Temperature Load Limit [pu] | |
| Turbine Factor [pu] | |
| Frictional losses factor pu [pu] | |
| Turbine Rated Power (=0→PN=Pgnn) [MW] | |
| Controller Minimum Output [pu] | |
| Controller Maximum Output [pu] |
gov_GGOV1, gov_PSSE_GGOV1
These PowerFactory components are mapped to GGOV1 component of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Load Limiter Reference Value [pu] | Any value |
| Turbine Gain [pu] | |
| No Load Fuel Flow [pu] | |
| Load Limiter Proportional Gain [pu] | |
| Load Limiter Time Constant [s] | |
| Temperature Detection Lead Time Constant [s] | |
| Temperature Detection Lag Time Constant [s] | |
| Acceleration Limiter Gain [pu/s] | |
| Acceleration Limiter Time Constant [s] | |
| Power Controller Reset Gain [pu] | |
| Electrical Power Transducer time constant [s] | |
| Governor Droop Feedback Signal Selector [-] | |
| Acceleration Limiter Setpoint [pu/s] | |
| Permanent Droop [pu] | |
| Speed Governor Deadband [pu] | |
| Governor Proportional Gain [pu] | |
| Governor Integral Gain [pu] | |
| Governor Derivative Gain [pu] | |
| Governor Derivative Controller Time Constant [s] | |
| Actuator Time Constant [s] | |
| Turbine Rated Power (=0→PN=Pgnn) [MW] | |
| Mechanical Damping Coefficient [pu] | |
| Switch for Fuel Source Coefficient [-] | |
| Turbine 2nd Factor [pu] | |
| Diesel Engine Transport Time Constant [s] | |
| Turbine Lead Time Constant [s] | |
| Turbine Lag Time Constant [s] | |
| Temperature Control [grd.F] | |
| Load Limiter Integral Gain [pu] | |
| Maximum Rate of Load Limit Decrease [pu/s] | |
| Minimum Speed Error Signal [pu] | |
| Minimum Valve Position Limit [pu] | |
| Maximum Valve Closing Rate [pu/s] | |
| Maximum Rate of Load Limit Increase [pu/s] | |
| Maximum Speed Error Signal [pu] | |
| Maximum Valve Position Limit [pu] | |
| Maximum Valve Opening Rate [pu/s] |
gov_HYGOV, gov_PSSE_HYGOV
These PowerFactory components are mapped to the HYGOV component of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Temporary Droop [pu] | Any value |
| Governor Time Constant [s] | |
| Filter Time Constant [s] | |
| Servo Time Constant [s] | |
| Water Starting Time [s] | |
| Turbine Gain [pu] | |
| frictional losses factor pu [pu] | |
| No Load Flow [pu] | |
| Permanent Droop [pu] | |
| Turbine Rated Power (=0->PN=Pgnn) [Mw] | |
| Minimum Gate Limit [pu] | |
| Gate Velocity Limit [pu] | |
| Maximum Gate Limit [pu] |
gov_IEEEG1, gov_PSSE_IEEEG1
These PowerFactory components are mapped to the IEEEG1 component of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Controller Gain [pu] | Any value |
| Governor Time Constant [s] | |
| Governor Derivative Time Constant [s] | |
| Servo Time Constant [s] | |
| High-Pressure Turbine Factor [pu] | |
| High-Pressure Turbine Factor [pu] | |
| Intermediate Pressure Turbine Time Constant [s] | |
| Intermediate Pressure Turbine Factor [pu] | |
| Intermediate Pressure Turbine Factor [pu] | |
| Medium Pressure Turbine Time Constant [s] | |
| Medium Pressure Turbine Factor [pu] | |
| Medium Pressure Turbine Factor [pu] | |
| High-Pressure Turbine Time Constant [s] | |
| Low-Pressure Turbine Time Constant [s] | |
| Low-Pressure Turbine Factor [pu] | |
| Low-Pressure Turbine Factor [pu] | |
| HP Turbine Rated Power (=0->PNhp=PgnnHp) [MW] | |
| LP Turbine Rated Power (=0->PNhp=Pgnnlp) [MW] | |
| Valve Closing Time [pu/s] | |
| Minimum Gate Limit [pu] | |
| Valve Opening Time [pu/s] | |
| Maximum Gate Limit [pu] |
gov_IEEEG2, gov_PSSE_IEEEG2
These PowerFactory components are mapped to IEEEG2 turbine governor of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Controller Gain [pu] | Any value |
| Governor Time Constant [s] | |
| Governor Derivative Time Constant [s] | |
| Servo Time Constant [s] | |
| Water Starting Time [s] | |
| Turbine Rated Power (=0→PN=Pgnn) [MW] | |
| Minimum Gate Limit [pu] | |
| Maximum Gate Limit [pu] |
gov_IEESGO, gov_PSSE_IEESGO
These PowerFactory components are mapped to the IEEESGO component of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Governor Time Constant [s] | Any value |
| Governor Derivative Time Constant [s] | |
| Controller Gain [pu] | |
| Servo Time Constant [pu] | |
| Steam Chest & Inlet Piping Time Constant [s] | |
| Low-Pressure Turbine Factor [pu] | |
| Interm. & Low-Pressure Turbine Time Constant [s] | |
| High-Pressure Turbine Factor [pu] | |
| Reheater Time Constant [pu] | |
| Turbine Rated Power (=0→PN=Pgnn) [MW] | |
| Minimum Gate Limit [pu] | |
| Maximum Gate Limit [pu] |
gov_TGOV1, gov_PSSE_TGOV1
These PowerFactory components are mapped the TGOV1 component of the Native Library.
Parameters from ElmDsl Section
Parameter | Description | Acceptable Values |
---|---|---|
| Turbine Delay Time Constant [s] | Any value |
| Turbine Derivative Time Constant [s] | |
| Turbine power coefficient [pu] | |
| Frictional Losses Factor [pu] | |
| Controller Droop [pu] | |
| Governor Time Constant [s] | |
| Minimum Gate Limit [pu] | |
| Maximum Gate Limit [pu] | |
| Turbine Rated Power (=0→PN=Pgnn) [MW] |