Documentation Home Page ePHASORSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Turbine Governors

On this page:

Notes

Version

Type Prefix

Version

Type Prefix

PowerFactory 2022 and prior versions

gov_

PowerFactory 2023 and more recent versions

gov_PSSE_

gov_GAST, gov_PSSE_GAST

These PowerFactory components are mapped to GAST component of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

R

Speed Droop [pu] 

Any value

T1

 Controller Time Constant [s]

T2

Actuator Time Constant [s]

T3

Compressor Time Constant [s]

AT

Ambient Temperature Load Limit [pu]

Kt

Turbine Factor [pu]

Dturb

Frictional losses factor pu [pu]

PN

Turbine Rated Power (=0→PN=Pgnn) [MW]

Vmin

Controller Minimum Output [pu]

Vmax

Controller Maximum Output [pu]

gov_GGOV1, gov_PSSE_GGOV1

These PowerFactory components are mapped to GGOV1 component of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

Ldref

Load Limiter Reference Value [pu]

Any value

Kturb

Turbine Gain [pu] 

Wfnl

No Load Fuel Flow [pu]

Kpload

Load Limiter Proportional Gain [pu]

Tfload

Load Limiter Time Constant [s]

Tsa

Temperature Detection Lead Time Constant [s]

Tsb

Temperature Detection Lag Time Constant [s]

Ka

Acceleration Limiter Gain [pu/s]

Ta

Acceleration Limiter Time Constant [s]

Kimw

Power Controller Reset Gain [pu]

Tpelec

Electrical Power Transducer time constant [s]

Rselect

Governor Droop Feedback Signal Selector [-]

Aset

Acceleration Limiter Setpoint [pu/s]

r

Permanent Droop [pu]

db

Speed Governor Deadband [pu]

Kpgov

Governor Proportional Gain [pu]

Kigov

Governor Integral Gain [pu]

Kdgov

Governor Derivative Gain [pu]

Tdgov

Governor Derivative Controller Time Constant [s]

Tact

Actuator Time Constant [s]

Trate 

Turbine Rated Power (=0→PN=Pgnn) [MW]

Dm

Mechanical Damping Coefficient [pu]

Flag

Switch for Fuel Source Coefficient [-]

bf1

Turbine 2nd Factor [pu]

Teng

Diesel Engine Transport Time Constant [s]

Tc

Turbine Lead Time Constant [s]

Tb

Turbine Lag Time Constant [s]

Tc

Temperature Control [grd.F]

Kiload

Load Limiter Integral Gain [pu]

rdown

Maximum Rate of Load Limit Decrease [pu/s]

minerr

Minimum Speed Error Signal [pu]

Vmin

Minimum Valve Position Limit [pu]

rclose 

Maximum Valve Closing Rate [pu/s]

rup

Maximum Rate of Load Limit Increase [pu/s]

maxerr

Maximum Speed Error Signal [pu]

Vmax

Maximum Valve Position Limit [pu]

ropen

Maximum Valve Opening Rate [pu/s]

gov_HYGOV, gov_PSSE_HYGOV

These PowerFactory components are mapped to the HYGOV component of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

r

Temporary Droop [pu]

Any value

Tr

Governor Time Constant [s] 

Tf

Filter Time Constant [s] 

Tg

Servo Time Constant [s]

Tw

Water Starting Time [s]

At

Turbine Gain [pu]

Dturb

frictional losses factor pu [pu]

qnl

No Load Flow [pu]

R

Permanent Droop [pu]

PN

Turbine Rated Power (=0->PN=Pgnn) [Mw]

Gmin

Minimum Gate Limit [pu]

Velm

Gate Velocity Limit [pu]

Gmax

Maximum Gate Limit [pu]

gov_IEEEG1, gov_PSSE_IEEEG1

These PowerFactory components are mapped to the IEEEG1 component of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

K

Controller Gain [pu]

Any value

T1

Governor Time Constant [s] 

T2

Governor Derivative Time Constant [s] 

T3

Servo Time Constant [s]

K1

High-Pressure Turbine Factor  [pu]

K2

High-Pressure Turbine Factor  [pu]

T5

Intermediate Pressure Turbine Time Constant [s]

K3

Intermediate Pressure Turbine Factor [pu]

K4

Intermediate Pressure Turbine Factor [pu]

T6

Medium Pressure Turbine Time Constant [s]

K5

Medium Pressure Turbine Factor [pu]

K6

Medium Pressure Turbine Factor [pu]

T4

High-Pressure Turbine Time Constant [s]

T7

Low-Pressure Turbine Time Constant [s]

K7

Low-Pressure Turbine Factor [pu]

K8

Low-Pressure Turbine Factor [pu]

PNhp

HP Turbine Rated Power (=0->PNhp=PgnnHp) [MW]

PNlp

LP Turbine Rated Power (=0->PNhp=Pgnnlp) [MW]

Uc 

Valve Closing Time [pu/s]

Pmin

Minimum Gate Limit [pu]

Uo

Valve Opening Time [pu/s]

Pmax

Maximum Gate Limit [pu]

gov_IEEEG2, gov_PSSE_IEEEG2

These PowerFactory components are mapped to IEEEG2 turbine governor of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

K

Controller Gain [pu]

Any value

T1

Governor Time Constant [s] 

T2

Governor Derivative Time Constant [s] 

T3

Servo Time Constant [s]

T4

Water Starting Time [s]

PN

Turbine Rated Power (=0→PN=Pgnn) [MW]

Pmin

Minimum Gate Limit [pu]

Pmax

Maximum Gate Limit [pu]

gov_IEESGO, gov_PSSE_IEESGO

These PowerFactory components are mapped to the IEEESGO component of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

T1

Governor Time Constant [s] 

Any value

T2

Governor Derivative Time Constant [s] 

K1

Controller Gain [pu] 

T3

Servo Time Constant [pu] 

T4

Steam Chest & Inlet Piping Time Constant [s]

K3

Low-Pressure Turbine Factor [pu]

T6

Interm. & Low-Pressure Turbine Time Constant [s]

K2

High-Pressure Turbine Factor [pu]

T5

Reheater Time Constant [pu]

PN

Turbine Rated Power (=0→PN=Pgnn) [MW]

Pmin

Minimum Gate Limit [pu]

Pmax

Maximum Gate Limit [pu]

gov_TGOV1, gov_PSSE_TGOV1

These PowerFactory components are mapped the TGOV1 component of the Native Library.

Parameters from ElmDsl Section

Parameter

Description

Acceptable Values

Parameter

Description

Acceptable Values

T3

Turbine Delay Time Constant [s]

Any value

T2

Turbine Derivative Time Constant [s]

At

 Turbine power coefficient [pu]

Dt

 Frictional Losses Factor [pu]

R

Controller Droop [pu]

T1

Governor Time Constant [s]

Vmin

Minimum Gate Limit [pu]

Vmax

Maximum Gate Limit [pu]

PN

Turbine Rated Power (=0→PN=Pgnn) [MW]

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter