Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »


This block is used to detect abnormal conditions in the grid’s frequency. For this purpose, a set of regions can be specified by the user as per [1]. A maximum of 8 different regions can be specified for over and under frequency events, respectively. Also, this block detects when the average ROCOF is above a specific threshold. 

Mask and Parameters

Configuration

NameDescriptionUnit

Sample Time (s)

Computational time step

s

Over-Frequency Range

NameDescriptionUnit

Number of Over-Frequency Points

Number of over-frequency regions delimited by a set of frequency points

-

Frequency Points (Hz) [Point1,…, Point 8]

Limit frequency values before reaching the respective over-frequency trip region

Hz

Frequency Points (s) [Point1,…, Point 8]

Amount of time that the converter must operate in a frequency region before tripping

s

Under-Frequency Range

NameDescriptionUnit

Number of Under-Frequency Points

Number of under-frequency regions delimited by a set of frequency points

-

Frequency Points (Hz) [Point1,…, Point 8]

Limit frequency values before reaching the respective under-frequency trip region

Hz

Frequency Points (s) [Point1,…, Point 8]

Amount of time that the converter must operate in a frequency region before tripping

s

ROCOF

  

NameDescriptionUnit

ROCOF Threshold

Maximum allowed ROCOF value before activating trip signal

Hz/s

Averaging Time Window (sec)

Time constant for the first order average filter block for the ROCOF estimation.

s

Inputs, Outputs and Signals Available for Monitoring

Inputs

NameDescriptionUnit

Freq

Grid frequency

Hz

Outputs

NameDescriptionUnit

U/O F

Trip signal for under or over frequency events

-

ROCOF

Trip signal for ROCOF events

-

References

[1]

IEEE, "IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces," IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003), no. doi: 10.1109/IEEESTD.2018.8332112, pp. 1-138, 2018.

[2]

IEEE, "IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces," IEEE Std 1547.1-2020, pp. 1-282, 2020.

Intellectual Property Disclaimer

Natural Resources Canada owns all intellectual property rights in the Smart Inverter Modelling Toolbox software and related products.

  • No labels