Turb_mod | Selection of turbine and shaft model. (Internal: actual model; External: model supply by user) |
Turb_on | Selection of turbine operation. (On=Normal operation; Off=constant power equal to power reference Peo/baseMW) |
Shaft_on | Selection of shaft operation. (On=Normal operation; Off=constant speed equal to speed reference wo) |
tb_Beta | Effect of speed variation on the water height h |
tb_Tw | Water time response in penstock |
tb_H | Inertia constant (pu/MVA) |
tb_Kd | The damping coefficient |
tb_Kdstart | Damping coefficient of turbine at start-up time. This value helps to reach synchronism. (typically = 5) |
tb_TStart | Duration of turbine start-up (in seconds, typically 5 s) |
tb_wmax | Maximum limit of machine’s speed (pu) |
tb_wmin | Minimum limit of machine’s speed (pu) |
tb_Tg0 | Torque representing total mechanical losses (pu/MW*s) |
tb_gPm | Operation mode of machine (1 = turbine generator; 0 = synchronous compensator). Obsolete, please use Turb_on. |