Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Current »

Unblocking can only be done manually. To enable the converter, the user must:

  • Set the current reference to zero;
  • Initiate the enabling order. Regular pulses will be sent to the thyristors (instead of pulses from bypass thyristors).
  • Set the current or voltage reference to the desired value. After unblocking, the converter will adjust to this given value with a certain delay depending on the limits imposed by the rate of change limiters. To maintain the current margin, the current ramp on the rectifier cannot be slower than that of the inverter at start-up.


  • No labels