Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Generic Excitation Programmable Parameters

The parameters are shown in the block diagram of the excitation system (ex_Tr, ex_Ka, ex_Ta, ex_Kf, ex_Tf, ex_Vtmax, ex_Vtmin, ex_Vrmin, ex_Vrmax, ex_Efdfix, Exci_on). In addition, the excitation system can be off and set to a constant value. Moreover, the excitation system can be modeled externally by a user-defined model, depending on the state of exci_mod switch.

  • exci_on: Selection of excitation system operation. (On=Normal regulation; Off=constant excitation)
  • exci_mod: Selection of excitation system model. (Internal = actual model; External = model supply by user)
  • ex_Tr: Voltage measurement time constant, (sec)
  • ex_Ka: Voltage regulator gain
  • ex_Ta: Voltage regulator time constant (sec)
  • ex_Kf: Damping filter feedback gain
  • ex_Tf: Damping filter feedback time constant (sec)
  • ex_Kp: Proportional gain on voltage limit
  • ex_Vtmin: Minimum static limit on voltage measurement (pu)
  • ex_Vtmax: Maximum static limit on voltage measurement (pu)
  • ex_Vrmin: Minimum static limit of excitation voltage (pu)
  • ex_Vrmax: Maximum static limit of excitation voltage; The maximum limit applied to the regulator transfer function is always the minimal value between the output of the Kp gain and the ex_Vrmax value.
  • ex_Efdfix: Constant excitation voltage. Used when Exci_on is off.

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323