Rectifier/Inverter 6/12 Pulse Dc Controllers | Protection
DC fault protection (on rectifier)
- Detection delay: Detection delay of DC fault (seconds);
- Vd threshold: DC voltage threshold used for DC fault detection (pu);
- α delay: Value of the constant α angle imposed after a fault is detected (degrees);
- α delay duration: Time interval during which the value of the forced α angle is imposed by the DC protection system. (seconds);
- α delay number: Number of times the constant α angle is imposed and then removed before the converter is automatically blocked by the DC fault protection;
Protection against commutation failure (inverter)
- ON/OFF Protection (1/0): “1” enables protection, “0” disables protection;
- γcf: Value added to the lower limit of γ by the protection for commutation failures (degrees);
- Rise time: First order time constant affecting the increase of minimum γ (seconds);
- Fall time: First order time constant affecting the decrease of minimum γ (seconds);