Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

59 - Overvoltage Relay

Summary

The over-voltage relay (59) operates when the voltage it monitors exceeds a set of threshold values. There are five levels of settings available in this relay. Each level corresponds
to a predefined over-voltage level and a tripping delay time. Two types of operating quantities are available: Phase-Neutral Voltage and Phase-Phase Voltage. The model works for 50 Hz or 60 Hz systems.

Icons and diagrams

Model overview
The over-voltage relay trips electrical equipment under its protection whenever the line or phase voltage exceeds the selected setting. A time-delay is normally used to enable it to ride through momentary spikes and thus prevent nuisance tripping. The five-level over-voltage relay characteristics are presented below. For instance, if we use the default values illustrated in Figure 3 - 9, Level 1 voltage is 1.05 pu and tripping time is 2 sec. It means that when the input voltage is higher than 1.05 pu and continues to be higher than 1.05 pu for more than 2 seconds, the over-voltage relay will be asserted. If the voltage is higher than 1.05 pu for any time that is less than 2 seconds, its timer will be reset and will not restart until the voltage reaches the level 1 voltage threshold again. All voltage levels and delay times are tunable parameters.

Over-voltage relay characteristics


Parameters

Figure 3 - 9 shows the control panel of the over-voltage relay model. The following parameters can be modified:

Relay parameter panel


The following parameters are tunable:

Parameters tab of 59 Relay

NameUnitDescriptionSample value
FrequencyHz

The frequency of the measured current signals. Both 50
and 60 Hz are supported within the model.

60
UbaseVThe base voltage (L-L) at the measurement location500000

Operating
Quantity

N/A

Two types of operating quantity are provided in this
model:
maximum Phase-Neutral Voltage or maximum Phase-
Phase Voltage among three phases.

Phase-Neutral
Voltage

Level 1puOvervoltage level 1.1.05
Level 2puOvervoltage level 2.1.1
Level 3puOvervoltage level 3.1.15
Level 4puOvervoltage level 4.1.2
Level 5puOvervoltage level 5.1.25
Time 1sTime delay associated with Level 1.2
Time 2sTime delay associated with Level 2..5
Time 3sTime delay associated with Level 3..4
Time 4sTime delay associated with Level 4..3
Time 5sTime delay associated with Level 5..2

Input and output signals
The module has 2 inputs and 2 outputs:

59 Relay I/O

I/O nameType (unit)Description
VabcInput (V)

A 3-dimension voltage input for three-phase voltages, in the order
of Va, Vb and Vc.

ResetInput (binary)

The reset signal for the relay. The relay will be reset when
this signal becomes 1.

QOutput (binary)

The output of over-voltage relay. By default it is 0, if an
over-voltage scenario is detected, it becomes 1.

Q_nOutput (binary)The complementary value of Q.



OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323