Firing (0 = internal, 1 = external, Simulink=2, Control Block=3): Specifies the source of firing pulses;
...
- KI Id: Integral gain of the PI current regulator (degrees/pu/second);
- KP Id: Proportional gain of the PI current regulator (degrees/pu/second);
- αmin: Lower limit of the delay angle α (degrees);
- αmax: Upper limit of the delay angle α (degrees).
- Δα1, Δα2: Limit values for the positive variation of delay angle α (degrees)) (See Figure 11-11);
- Δα3, Δα4: Limit values for the negative variation of delay angle α (degrees) (See Figure 11-11);
...
- KI Id: Integral gain of the PI current regulator (degrees/pu);
- KP Id: Proportional gain of the PI current regulator (degrees/pu);
- KI Vd: Integral gain of the PI voltage regulator (degrees/pu);
- KP Vd: Proportional gain of the PI voltage regulator (degrees/pu);
- γmin: Lower limit for the γ angle (degrees);
- αmin: Lower limit for the α angle (degrees);
- Id Margin: Current margin (pu);
- Vd Margin: Voltage margin (pu);
- Δα1, Δα2: Limit values for the positive variation of delay angle α (degrees) (See Figure 11-11);
- Δα3: Limit value for the negative variation of delay angle α (degrees) (See Figure 11-11);
...