This section presents the list of components from the EMTP libraries that are partially supported when the EMTP models are loaded in HYPERSIM. These blocks are compatible with an HYPERSYM simulation. However, some of their options are not supported in HYPERSIM. The first column indicates the name of the block in EMTP while the second column indicates the equivalent name of the component in HYPERSIM. The third column lists the options that are not supported in HYPERSIM.

Control

Component in EMTP

Name in HYPERSIM

Incompatibility

delay

delay

Arbitrary pulse delay mode not supported

derivative

derivative

End-step du/dt, and Mid-step d2u/dt2 modes not supported

table function

Floating-point constant

The maximum number of rows supported is 500

Lines

Component in EMTP

Name in HYPERSIM

Incompatibility

CP line/cable m-phase

Constant param, m-ph

HS models only support 1, 2, 3, 4, 6, 9, and 12 phases

Loads

Component in EMTP

Name in HYPERSIM

Incompatibility

PQ load with load-flow

PQ load with load-flow

Negative Power value not supported. Power will be set to 0. Visible ground pin not supported.

Machines

Component in EMTP

Name in HYPERSIM

Incompatibility

Asynchronous

Induction motor with cage rotor

Steady-state initialization and total saturation are not supported.

Saturation data in D-axis is limited to 10 points.

Saturation data in Q-axis is not considered in HYPERSIM.

Deep bar factor not supported.

Lock rotor shaft for negative speed is not supported.

Absolute speed damping is not supported.

HYPERSIM supports only WYE grounded connection for the armature winding.

Rotor speed control is not supported.

The Multi-masses model is not supported.

Mechanical torque in pu control is not supported.

Synchronous

Synchronous machine

HYPERSIM uses EL 1.0 and EU 1.2 for saturation in D-axis.

Sgu is smaller than Sgl. Values swapped.

Saturation data in Q-axis is not considered in HYPERSIM.

HYPERSIM does not support Canay impedance in extra data.

HYPERSIM only represents 1 damper in the D axis.

HYPERSIM only supports 2 dampers in the Q axis.

HYPERSIM support only WYE grounded connection for the armature winding.

HYPERSIM supports only open circuit data (D Axis).

HYPERSIM supports only open circuit data (Q Axis).

The Multi-masses model is not supported.

Meters

Component in EMTP

Name in HYPERSIM

Incompatibility

Control signal meter

Control signal meter

RMS meter not supported

Current scope and observe

I measurement, 1ph

v and p observables not supported

Simulation probe

Simulation probe

Simulation stop time and Base Frequency not supported

Nonlinear

Component in EMTP

Name in HYPERSIM

Incompatibility

L nonlinearSeries nonlinear LNegative values are not supported
ZnOSeries nonlinear R

HYPERSIM supports a maximum of 10 exponential segments.

v, p, e observables not supported.

Exponential segments after flashover not supported

RLC branches

Component in EMTP

Name in HYPERSIM

Incompatibility

PIPISingle-phase line not supported
PI smallPI smallSingle-phase line not supported

Sources

Component in EMTPName in HYPERSIMIncompatibility

AC current source

AC current source

Unsupported start and stop time

AC voltage source

AC voltage source

Serial voltage source not supported.

Unsupported start and stop time

AC voltage source (3-ph)

AC V source

Unsupported start and stop time

AC voltage source and impedance

AC voltage source and impedance

Unsupported connections to pink

Visible ground pin not supported

Unsupported start and stop time

Controlled current source

Controlled I source, 1-ph

Unsupported start and stop time

Controlled voltage source

Controlled V source, 1-ph

Unsupported start and stop time

Load-Flow Bus

Load-Flow equivalent

HYPERSIM only supports Positive Sequence R impedance

HYPERSIM only supports Positive Sequence L impedance

Remote control bus not supported

R must be entered as Sequence Data

L must be entered as Sequence Data

Switches

Component in EMTPName in HYPERSIMIncompatibility

Controlled switch

Controlled switch

v and p observables not supported

Diode (ideal)

Diode

Closed at T0 not supported

Ideal switch

Circuit breaker, 1-ph

v and p observables not supported

Ideal switch : Breaker Symbol

Circuit breaker, 1-ph

v and p observables not supported

Thyristor (ideal)

Thyristor (ideal)

v and p observables not supported

Closed at T0 not supported

Transformers

Component in EMTPName in HYPERSIMIncompatibility

ideal unit m-windings

ideal unit m-windings

HYPERSIM only support one secondary winding with a controlled ratio

HYPERSIM only supports a maximum of two secondary windings

Three-phase nameplate input

2 winding

HYPERSIM doesn't support

R1 <= 0, using R1 = 1E-6

L1 < 1E-6  pu, using L1 = 1E-6 pu

R2 <= 0, using R2 = 1E-6

L2 < 1E-6  pu, using L2 = 1E-6 pu

Using Rm and Lm = 30000 pu for linear transformer

Primary and secondary neutral impedance values must be entered manually.

Exported mask not supported

YgYgD nameplate input O

3 winding, w/sat

HYPERSIM doesn't support

R1 <= 0, using R1 = 1E-6

L1 < 1E-6  pu, using L1 = 1E-6 pu

R2 <= 0, using R2 = 1E-6

L2 < 1E-6  pu, using L2 = 1E-6 pu

R3 <= 0, using R3 = 1E-6

L3 < 1E-6  pu, using L3 = 1E-6 pu

Using Rm and Lm = 30000 pu for linear transformer

Exported mask not supported