Documentation Home Page HYPERSIM Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 3 Current »

Supported Features

  • Supports TCP protocol
  • Supported IEC 60870-5-104 commands:
    • General interrogation
    • Specific group interrogation
    • Single point write
    • Double point write
    • Regulating step write
    • Bitstring write
    • Normalized measurand write
    • Scaled measurand write
    • Floating point measurand write
    • Clock synchronization
  • Supports IEC 60870-5-104 point control mode:
    • Select/Execute
    • Select only
    • Execute only
  • Support multiple slave
  • Each slave can have its own IP address (IP aliasing feature)
  • Each point input can be initialized by the user
  • Each point can be attached to a specific interrogation group or to the cyclic group
  • Event scan can be enabled for each data types to trigger spontaneous data report to the master
  • Each analog point has a configurable low limit, high limit and deadband
  • Configurable event scan rate
  • Configurable maximum number of buffered of event for each data types
  • Configurable cause of transmission (COT) size (1 or 2 octets)

Limitations

  • It operates asynchronously from the model simulation step. It will try to send and receive data as fast as possible. A dedicated core can be used to improve performance.
  • The event scan rate is a global parameter for the entire database. It will be the same of all types of data.
  • Only TCP communication is supported.
  • Each configured slave must have a unique ASDU address.
  • RMS computation is only available for floating point outputs.
  • No labels