IEEEST
Description
This model is based on the PowerSystem Stabilizer (PSS) IEEEST from [1] and [2]. The architecture of the IEEEST is shown below.
Mask and Parameters
IEEEST Parameters
Expanding the “Block diagram” displays the IEEEST diagram in the parameters window.
Name | Description | Unit |
---|---|---|
Input Type | Type of Input (Reference from Input Types Table below) | - |
A1, A2, A3, A4, A5, A6 | Notch filter Parameters | - |
T1, T3 | Lead compensating time constants | s |
T2, T4 | Lag compensating time constants | s |
T5, T6 | Washout time constant | s |
Ks | Stabilizer gains | - |
Lsmax | Stabilizer maximum output | pu |
Lsmin | Stabilizer minimum output | pu |
Vcl | Stabilizer input Vct lower cutoff threshold | pu |
Vcu | Stabilizer input Vct upper cutoff threshold | pu |
The input of IEEEST can be of any type as mentioned above, based on the control requirements. For each type of input, the corresponding reference input is provided as given in the InputTypes Table.
Input Types Table
Input Type | Name | Description |
---|---|---|
1 | Rotor Speed (pu) | Reference speed (pu) w* of the Syn. generator. |
2 | Bus frequency (pu) | Reference frequency (pu) f* of the Syn. generator. |
3 | Generator electrical power on MBASE base (pu) | Reference Electrical power output (pu) Pe0* of the syn. generator. |
4 | Generator accelerating power (pu) = Pm – Pe0 | Reference input = 0 |
5 | Bus voltage (pu) | Reference voltage (pu) Vt* |
6 | Derivative of pu bus voltage | Reference input = 0 |
Initial Values
Name | Description | Unit |
---|---|---|
Input Reference | Reference to the input | - |
Inputs, Outputs and Signal Available for Monitoring
Inputs
Name | Description | Unit |
---|---|---|
Input | The input is one of the following type:
| pu |
Vct | Compensator terminal voltage of a remote bus for inputs 2, 5 & 6. This may be neglected if the threshold voltages Vcl & Vcu are zero. | pu |
Outputs
Name | Description | Unit |
---|---|---|
Vs | Power system stabilizer model output | pu |
References
[1] Siemens Industry, Inc. Siemens Power Technologies International, "PSS®E 34.2.0 MODEL LIBRARY," April 2017.
[2] IEEE, "IEEE Recommended Practice for Excitation System Models for Power System Stability Studies," IEEE Std 421.5-1992, pp. 1-56, 10 Aug. 1992.