Documentation Home Page ARTEMiS Home Page
Pour la documentation en FRANÇAIS, utilisez l'outil de traduction de votre navigateur Chrome, Edge ou Safari. Voir un exemple.

Curtailment Power Controller

Page Content

This module facilitates the user to interface with the power curtailment block that governs the power distribution between the wind-turbine (WT) and photo-voltaic (PV) generation systems.

Mask and Parameters

Main Parameter Tab

Name

Unit

Description

Name

Unit

Description

Sample Time

s

This parameter allows the user to specify the block sample time in seconds.

PVGS and WTGS Parameters Tab

Name

Unit

Description

Name

Unit

Description

Trip signal time delay

s

Apply a time delay to the generator trip signal in seconds.

Minimum curtailment power

pu

Specify the minimum power in per-unit that can trigger the curtailment signal.

Maximum curtailment power

pu

Specify the maximum power threshold beyond which the generation system will trip.

Curtailment signal time delay

s

Apply a time delay to the curtailment signal in seconds.

Power difference deadzone limits [MIN MAX]

pu

Specify the minimum and maximum limits of the deadzone for the difference between the set reference power and curtailment power.

Power difference saturation limits [UPPER LOWER]

pu

Specify the lower and upper bounds of the saturation for the difference between the set reference power and curtailment power.

Inputs, Outputs, and Signals Available for Monitoring

Inputs

Name

Unit

Description

Name

Unit

Description

PV P ref

pu

Reference power for the PV generation system in per-unit.

WT P ref

pu

Reference power for the WT generation system in per-unit.

Curtail P ref

pu

Power reference to be curtailed in per-unit.

Outputs

Name

Unit

Description

Name

Unit

Description

P ref WT

 

Reference power output for the WTGS.

Curtail enable WT

 

WTGS curtailment status. 1: cutailment on; 0: curtailment off.

P ref PV

 

Reference power output for the PVGS.

curtail enable PV

 

PVGS curtailment status. 1: cutailment on; 0: curtailment off.

PV trip

 

PVGS Trip signal status. 1: the unit is tripped; 0: the unit is not tripped.

WT trip

 

WTGS Trip signal status. 1: the unit is tripped; 0: the unit is not tripped.

Curtail enable

 

Curtailment signal status. 1: curtailment is in effect; 0: curtailment is not in effect

OPAL-RT TECHNOLOGIES, Inc. | 1751, rue Richardson, bureau 1060 | Montréal, Québec Canada H3K 1G6 | opal-rt.com | +1 514-935-2323
Follow OPAL-RT: LinkedIn | Facebook | YouTube | X/Twitter